9.2
Acquisition procedure:
PROG
AP P-
x4 s
OPENING
OPEN
• Press and hold PROG for 4 seconds.
• Turn the release pin, the message
calibration procedure. The operating parameters of the motor are determined during calibration.
• If the motor calibration procedure is successful, the message
• Return release pin. The acquisition procedure now starts.
is shown on the display (only if parameters
beam within 5 s, to prevent interrupting the procedure.
is shown on the display and the gate starts opening at low speed.
• The gate closes until it reaches the gate closed limit switch.
If the acquisition procedure is completed successfully, the display enters the command and safety device state display
mode.
If the following error messages are shown on the display, repeat the acquisition procedure:
: calibration procedure failed.
: acquisition error. Press the TEST button to clear the error, and check the safety device in alarm state.
: travel length error. Press the TEST button to clear the error, and check that gate is completely closed.
ATTENTION: if the acquisition procedure was successful BUT the space between the leaf (stopped at the limit
switch) and the mechanical stop is not as desired (at least 3cm), move the limit switch and REPEAT THE
ACQUISITION PROCEDURE. Ensure that AT LEAST 3 centimetres remain between the leaf stop and the mechanical
stop.
For more information, see chapter 16 "Alarms and faults".
PH A5
PH A5
PH
A5
AU to
AU
to
CLOSING
is shown on the display.
appears on the display after a few seconds. The controller unit launches a
,
,
FO
FO TO
(if FT are connected
or enabled)
CLOSE
,
are not disabled). Keep away from the photocell
x5 s
TO
AU to
Yes