Installing the Drive

Electrical Installation

IMPORTANT: Read the Safety Information on page Cont. 2 before proceeding.

Wiring Instructions

Minimum Connections for Application 1:
To motor thermistor,
or link terminals
TH1A and TH1B
Note:

Local Control Wiring

This is the simplest installation. Every new drive will operate in
Local Control when first powered-up. The keypad is used to start
and stop the drive.
Refer to the Connection Diagram and install the:
Thermistor cable, or link/jumper terminals TH1A and TH1B
if not used (we recommend you use a thermistor)
Motor cable
Supply cable
Follow the earthing/grounding and screening advice
Refer to Chapter 4: "Operating the Drive"- Local Control
Operation.

Remote Control Wiring

If operating in Remote Control you will use your control panel to start and stop the drive, via a
speed potentiometer and switches or push-buttons.
Your wiring of the control terminals will be governed by the Application you use: refer to
Chapter 12 for an explanation of the various Applications you can select and the appropriate
control wiring. Application 1 is the default Application.
The diagram below shows the minimum connections to operate the drive for single-wire
(switch) starting, and push-button starting. Other control connections for your Application,
shown in Chapter 12, and can be made to suit your system.
Referring to the Connection Diagram:
Follow the instructions for Local Control Wiring, as detailed above
Install using minimum connections (suitable for Application 1only), or refer to Chapter 12
and install the appropriate control wiring for your system
DIN1
+24V
+10V REF
AIN1
0V
You can still operate the drive in Local mode, if necessary, with any Application selected.
Refer to Chapter 4: "Operating the Drive" and follow the relevant instructions for Single Wire
Starting or Push-Button Starting.
This product is designated as "professional equipment"
as defined in EN61000-3-2. Where enforced, permission of the supply authority shall
be obtained before connection to the low voltage domestic supply.
Ensure that all wiring is electrically isolated and cannot be made "live"
The drive is suitable for use with both earth referenced supplies (TN) and non-
earth referenced supplies (IT) when fitted with an internal ac supply EMC filter.
Single Wire Starting
2-position
switch
7
Start
6
4
2
Speed
Reference
1
WARNING!
unintentionally by other personnel.
Minimum Connections
To motor thermistor,
or link terminals
TH1A and TH1B
Push-Button Starting
10
DIN4/DOUT2
Start
7
DIN1
6
+24V
4
+10V REF
2
AIN1
1
0V
Stop
normally-closed
pushbutton
normally-open
pushbutton
Speed
Reference