G
ETTING
1
Introduction
Note:
Equipment Inspection
Storage and Packaging
About this Manual
Note: Please read all Safety Information before proceeding with the installation and operation
650 Series AC Drive
S
TARTED
The 650 Series AC Drive provides simple, compact, and low-cost speed control for 3-phase
induction motors.
It operates as an Open-loop Inverter (V/F Fluxing).
This manual describes the low-power end of the 650 product range for the following motor
power ratings:
Nominal Input Voltage
Frame 1
230V
Frame 2
230V
Frame 2
400V
Frame 3
230V
Frame 3
230V
Frame 3
400V
The drive features:
Local or Remote mode operation
Support for RS485 and Modbus RTU comms protocols
SELV control terminals (Safe Extra Low Volts)
Intelligent monitoring strategy to avoid nuisance tripping
In-built protection of the unit against overloads, excessive voltages, phase-to-phase and
phase-to-earth short circuits
An internal RFI filter is fitted as standard
An internal dynamic brake switch for connection to an external resistor (Frame 3: 230V, and
400V units only)
Quiet operation
Do not attempt to control motors whose rated current is less than 50% of the drive rated
current. Poor motor control or Autotune problems may occur if you do.
Check for signs of transit damage
Check the drive is suitable for your requirements by reading the Product Code on the rating
label. Refer to Chapter 9: "Technical Specifications" - Understanding the Product Code.
If the unit is damaged, refer to Chapter 8: "Routine Maintenance and Repair" for information on
returning damaged goods.
Save the packaging in case of return. Improper packaging can result in transit damage.
If the unit is not being installed immediately, store the unit in a well-ventilated place away from
high temperatures, humidity, dust or metal particles.
This manual is intended for use by the installer, user and programmer of the drive. It assumes a
reasonable level of understanding in these three disciplines.
of this unit.
It is important that you pass the manual on to any new user of this unit.
Software Product Manual
An accompanying Software Product Manual is available for download from the Parker website:
www.parker.com/ssd
Getting Started
Phase
Drive Power
1
0.25 – 0.75kW
1
1.1 – 1.5kW
3
0.37 – 2.2kW
1
2.2kW
3
2.2 – 4.0kW
3
3.0 – 7.5kW
1-1
0.3 - 1.0 Hp
1.5 - 2.0 Hp
0.5 - 3.0 Hp
3.0 Hp
3.0 - 5.0 Hp
4.0 - 10.0 Hp