6-3
Programming Your Application
MMI Parameters Table
Display
Parameter
FIXED BOOST
M VF
PASSWORD
Parameters
P
301 to
P
308 are visible in the PAR menu when Application 3 is selected in parameter
PRESET 0
PRESET 1
PRESET 2
PRESET 3
PRESET 4
PRESET 5
PRESET 6
PRESET 7
Parameters
401 to
404 are visible in the PAR menu when Application 4 is selected in parameter
P
P
R/L RAMP TIME
R/L MAX VALUE
R/L MIN VALUE
R/L RESET VALUE
Parameters
P
501 and
P
506 are visible in the PAR menu when Application 5 is selected in parameter
PI P GAIN
PI I GAIN
PID D GAIN
F
PID D FILTER TC
F
PID FEEDBACK
GAIN
F
PID LIMIT
F
PID SCALING
F
Description
Used to correctly flux the motor at low speeds. This
allows the drive to produce greater starting torque
for high friction loads. It increases the motor volts
above the selected V/F characteristic at the lower
end of the speed range
OUTPUT VOLTS
100%
INCREASED
TORQUE
FLUXING
NORMAL FLUXING
25%
INCREASING
BOOST
0%
f B
= BASE FREQUENCY
A password may be set to prohibit unauthorised
adjustment of parameters. When
non-zero you will be required to match this value
before parameters can be adjusted
A user-adjustable speed preset, set by
potentiometer
A user-adjustable speed preset
A user-adjustable speed preset
A user-adjustable speed preset
A user-adjustable speed preset
A user-adjustable speed preset
A user-adjustable speed preset
A user-adjustable speed preset
The time taken to ramp the Raise/Lower output
from 0.00% to 100.00% of its value
The maximum value for the ramp output
The minimum value for the ramp output
The value the output is set to when Reset is TRUE,
when DIN4 (terminal 10) is 24V in Application 4
The PI proportional gain
The PI integral gain
The PID derivative gain
In order to help attenuate high frequency noise on
the derivative term, a first order lag has been
provided. This parameter determines the filter time
constant.
A multiplier applied to the feedback signal of the
PID
Determines the maximum positive and negative
excursion (Limit) of the PID output
This parameter represents an overall scaling factor
which is applied after the PID positive and negative
limit clamps
Range
0.00 to 25.00%
CONSTANT
POWER RANGE
FREQUENCY
f B
0000 – FFFF
P
99 is set to
-100.00 to 100.00
-100.00 to 100.00
-100.00 to 100.00
-100.00 to 100.00
-100.00 to 100.00
-100.00 to 100.00
-100.00 to 100.00
-100.00 to 100.00
0.0 to 600.0s
-100.00 to 100.00%
-100.00 to 100.00%
-100.00 to 100.00%
0.00 to 100.00
0.00 to 100.00
0.00 to 100.00
0.05 to 10.00s
-10.00 to 10.00
0.00 to 300.00%
-3.0000 to 3.0000
Default
product
code
dependent
0000
P
1
-
20.00
50.00
100.00
-10.00
-20.00
-50.00
-100.00
1
P
10.0s
100.00%
0.00%
0.00%
P
1
0.10
1.00
0.00
0.05s
1.00
300.00%
1.0000
650 Series AC Drive