Installing The Drive; Connection Diagram - Parker 650 Serie Manual De Producto

Tabla de contenido

Publicidad

Connection Diagram

Frame 2
3 380-460V ac
(see Power Terminal Variations
inset for other frame sizes)
Volt - free
Contacts
Motor Thermistor
Supply Protective Earth/Ground
380-460V ac
3
external brake resistor
(400V unit only)
M
Motor Protective Earth/Ground
1 : RL1A, RL1B
Volt-free relay terminals can
be used as either `live' or SELV.
2 :TH1A, TH1B
Motor thermistor connections are
regarded as a `live circuit' and
must not be connected to SELV circuits.
only
screen and
earth wire
connections
shown for
clarity
*
Connect the 0V/COMMON to protective earth/ground.
In a system comprising more than one controller,
connect the 0V/COMMON signals and join to
protective earth/ground at one point only.
This is mandatory to meet the EMC specification stated.
Wiring Instructions
1 Remove the terminal cover from the drive.
2 Loosen the motor cable screen clamp.
3 Connect the power supply cable, motor cable and control cables (if required).
4 Fasten the motor cable in place with the motor cable screen clamp.
Secure any control cable screen connections under the right hand screw.
Frames 2 & 3 only : Secure control cables under the wire retainers.
5 Connect the thermistor and user - relay if required.
Frames 2 & 3 only: connect the dynamic brake if required (3 phase units only).
6 Use a cable tie and secure all the control cables and user -relay cables (if fitted)
as close to the control terminals as possible.
7 Connect the ancillary equipment as shown, for example, an external brake resistor.
8 Re-fit the terminal cover.
IMPORTANT:
Note that the 650 unit must be permanently earthed using two independent protective earth/ground incoming supply conductors.
650 Series AC Drive
RL1A
See Note 1
RL1B
TH1A
See
Note 2
TH1B
L1
L2/N
L3
DC+
DBR
screen
M1/U
M2/V
M3/W
Motor Screen Earth/Ground
Dynamic Brake Cable
Thermistor Cable
Motor Cable
Supply Cable
User Relay Cable
Control Cables
RS232
port
(future option)
P3
13 12 11
10
DIN4/DOUT2
9
DIN3/DOUT1
fix cable
tie here
8
DIN2
7
DIN1
6
+24V
5
AOUT1
4
+10V REF
3
AIN2
2
AIN1 *
1
0V
Wire Retainers
use
two
Screen Earth/Ground
separate
protective
earth
wires
1

Installing the Drive

To remove the T erminal Cover
press here and slide down
Refer to Chapter 12: "Applications"
for specific control wiring for each
Application
* If AIN1 is not used, connect to 0V
TH1A
TH1A
TH1B
TH1B
L1
L1
L2/N
L2/N
M1/U
L3
M2/V
DC+
M3/W
DBR
M1/U
Frame 1
220-240V ac
M2/V
M3/W
Frame 2
1
220-240V ac
Power Terminal
Variations
IT
Non-earth referenced
supply
The drive is suitable for use with earth
referenced supplies (TN) and non-earth
referenced supplies (IT) when
fitted with an internal ac supply EMC filter.
3-3
TH1A
TH1B
L1
L2
L3
DC+
DBR
DC
-
M1/U
M2/V
M3/W
Frame 3
3
220-240V ac
3
380-460V ac
TN
Earth referenced
supply

Publicidad

Tabla de contenido
loading

Tabla de contenido