Pplication; Mmi Parameters - Parker 650 Serie Manual De Producto

Tabla de contenido

Publicidad

6-1
Programming Your Application
P
ROGRAMMING
1

MMI Parameters

Note: The "Range" for a parameter value is given in the Configurable Parameters Table.
MMI Parameters Table
Display
Parameter
APPLICATION
MAX SPEED
M
MIN SPEED
ACCEL TIME
M
DECEL TIME
M
Y
OUR
You can program the drive to your specific application. This programming simply involves
changing parameter values. For instance, parameter
be used as starting points for application-specific programming.
Each Application internally re-wires the drive for a different use when it is loaded. The default
for the parameter is "1". Changing this parameter's setting to "2" will load Application 2. Refer
to Chapter 12: "Applications" for further information.
If necessary, there are three parameters for tuning your drive. Refer to PID - Tuning Your Drive,
page 6-8.
Saving Your Modifications
When parameter values are modified or an Application is loaded, the new settings are saved
automatically. The drive will retain the new settings during power-down.
This table provides information about each parameter accessible using the keypad, or MMI
(Man Machine Interface). For more information, refer to the 650 Software Product Manual on
our website:
www.parker.com/ssd
Key to MMI Parameters Table
Parameters indicated with
F
DETAILED MENUS parameter (
M
Parameters indicated with
Application using parameter
Ranges for outputs are given as "—.xx %", for example, indicating an indeterminate
integer for the value, to two decimal places.
MMI Parameters Table
Description
This parameter selects and loads the Application to
be used. APP 0 will not control a motor. APP 6, 7,
8 & 9 are reserved for future use.
Refer to the 650 Software Product Manual,
Chapter 5: "Applications" which gives detailed
information about each Application.
Note: Parameter values are changed to
factory settings by loading a new
Application, except Motor Parameters
(indicated
The frequency at which the 650 will run when
maximum setpoint is applied. The default can be
either 50 or 60Hz.
The minimum frequency at which the 650 will run,
as a percentage of the MAX SPEED parameter
The time taken for the 650 output frequency to
ramp up from zero to MAX SPEED
The time taken for the 650 output frequency to
ramp down from MAX SPEED to zero
A

PPLICATION

F
are visible with full menus only. Refer to the
ST
99).
M
are Motor Parameters. They are not reset by changing
P
1; all other parameters are reset to default values.
SET::PAR Menu
)
M
P
1 selects various Applications which can
Range
0= NULL
1= STANDARD
2= LOCAL/REM
(AUTO/MANUAL)
3= PRESETS
4= RAISE/LOWER
5= PID
6= APP 6
7= APP 7
8= APP 8
9= APP 9
7.5 to 300Hz
-100.0 to 100.0%
0.0 to 3000.0s
0.0 to 3000.0s
Default
1
product
code
dependent
0.0%
product
code
dependent
product
code
dependent
650 Series AC Drive