European Directives and the CE Mark

CE Marking for Low Voltage Directive

CE Marking for EMC - Who is Responsible?

Note: The specified EMC emission and immunity performance of this unit can only be achieved

EMC Compliance

Radiated Emissions
Immunity
Conducted Emissions
Conducted Emissions
650 Series AC Drive
Field Grounding Terminals
The field grounding terminals are identified with the International Grounding Symbol
(IEC Publication 417, Symbol 5019).
Operating Ambient Temperature
Devices are considered acceptable for use in a maximum ambient temperature of 40°C (can be
derated up to 50°C).
When installed in accordance with this manual, the 650 Series AC Drive is CE marked by
Parker Hannifin Manufacturing Limited in accordance with the low voltage directive (S.I. No.
3260 implements this LVD directive into UK law). An EC Declaration of Conformity (low
voltage directive) is included at the end of this chapter.
when the unit is installed to the EMC Installation Instructions given in this manual.
According to S.I. No. 2373 which implements the EMC directive into UK law, the requirement
for CE marking this unit falls into two categories:
1. Where the supplied unit has an intrinsic/direct function to the end user, then the unit is
classed as relevant apparatus. In this situation the responsibility for certification rests with
Parker Hannifin Manufacturing Limited. The Declaration of Conformity is included at the
end of this Chapter.
2. Where the supplied unit is incorporated into a higher system/apparatus or machine which
includes (at least) the motor, cable and a driven load but is unable to function without this
unit, then the unit is classed as a component. In this circumstance, the reponsibility rests
with the manufacturer/supplier/installer of the system/apparatus/machine.
All Models
All models are compliant with BS EN61800-3.
EN50081-1(1992) and EN61800-3 unrestricted distribution when mounted inside the
specified cubicle, see above. Control and motor cables must be screened and
correctly fitted with glands where they exit the cubicle. Control 0V must be connected
to protective earth/ground.
EN50082-1 (1997), EN61800-3 (1997), EN61000-6-2 (1999)
FRAME 1 & 2: 1-Phase (TN only),
EN50081-1(1992), EN61800-3 unrestricted distribution,
maximum motor cable length: 25m
FRAME 2 & 3 : 3-Phase, FRAME 3 : 1-Phase (TN only)
EN50081-2(1993), EN61800-3 restricted distribution
maximum motor cable length: 25m