Control Wiring Connections; Power Wiring Connections - Parker 650 Serie Manual De Producto

Tabla de contenido

Publicidad

3-4
Installing the Drive
Terminal
Description
(SELV)
P3
P3
RL1A
User Relay
RL1B
User Relay
10
DIN4/
DOUT2
9
DIN3/
DOUT1
8
DIN2
7
DIN1
6
+24V
5
AOUT1
4
10VREF
3
AIN2
2
AIN1
1
0V
Terminal
Description
TH1A
Thermistor
TH1B
Thermistor
Reference
Terminal
L1
Power Input
L2/N
Power Input
L2
L3
Power Input
No user connection
DC-
DC+
Dynamic
Brake
DBR
Dynamic
Brake
M1/U
Motor
M2/V
Outputs
M3/W
Reference
Terminal

Control Wiring Connections

Application 1 Default Function
(for other Applications refer to Chapter 12: "Applications")
RS232 port for use with remote-mounted RS232 keypad or
programming PC
Volt-free contact
Volt-free contact
Configurable digital input/output
Not Stop (input):
0V = No latching of Run (DIN1), 24V = Run latched
Jog – configurable digital input:
0V = Stop, 24V = Jog
Direction – configurable digital input:
0V = Forward, 24V = Reverse
Run – configurable digital input: 0V = Stop, 24V = Run
24V – 24V supply for digital I/O
Ramp Output – configurable analog output (10mA loading)
10V - 10V reference (10mA maximum loading)
Feedback – analog input 2
Setpoint – analog input 1.
If AIN 1 is not used, connect to 0V.
0V - 0V reference for analog/digital I/O

Power Wiring Connections

Function
Connection to motor
thermistor
Connection to motor
thermistor
Supply protective earth (PE). This terminal must be connected to a protective (earth)
ground for permanent earthing.
Single and three
phase live
connection
Single phase neutral
(or L2 three phase
live connection)
Three phase live
connection
Connection to
external brake
resistor
Connection to
external brake
resistor
Connection for
motor
Supply protective earth (PE). This terminal must be connected to a protective (earth)
ground for permanent earthing.
200V 1-Phase
It is good practice to protect motors by fitting temperature
sensitive resistors. A typical resistance (up to a reference
temperature of 125C) is 200, rising rapidly to 2000 above
this temperature. Connect devices in series between TH1A and
TH1B. Link the terminals if temperature sensors are not used.
220/240V ac ±10% rms with
respect to L2/N. 50-60Hz
(IT/TN)
220/240V ac ±10% with
respect to L1. 50-60Hz
(IT/TN)
Not applicable
Not applicable
Not applicable
Motor rated at:
0 to 220/240V ac
0 to 240Hz
Range
-
0-250Vac/24Vdc 4A
0-250Vac/24Vdc 4A
0-24V source open
collector 50mA
maximum
0-24V
0-24V
0-24V
50mA maximum
0-10V
10V
0-10V, 4-20mA
0-10V
0V
Range
200V/400V 3-Phase
220/240V or 380/460V ac
±10% rms with respect to L2, L3
phase-to-phase. 50-60Hz
(IT/TN)
220/240V or 380/460V ac
±10% with respect to L1, L3.
50-60Hz (IT/TN)
220/240V or 380/460V ac
±10% with respect to L1, L2.
50-60Hz (IT/TN)
Frame 2 (high volt only) & 3.
See "Internal Dynamic Brake
Switch" table
Frame 2 (high volt only) & 3.
See "Internal Dynamic Brake
Switch" table
Motor rated at:
0 to 220/240V or 380/460V ac
0 to 240Hz
650 Series AC Drive

Publicidad

Tabla de contenido
loading

Tabla de contenido