Selection and Ordering data
Pointek CLS300 - Digital - Cable with
Threaded or Flanged process connection
Inverse frequency shift capacitance level and
material detection switch with optional rod/cable
choices and configurable output. It is ideal for
detecting liquids, solids, slurries, foam, and inter-
faces in demanding conditions where high pres-
sure and temperatures are present and has the
ability to tune out buildup on the probe.
Thermal isolator
Without thermal isolator
With thermal isolator [for process connection
temperatures over 85 °C (185 °F)]
Wetted seals
FKM
FFKM [for process temperatures above -20 °C (-4 °F)]
Probe material
Bare 316L stainless steel cable, PEEK isolators and
316L stainless steel cable weight
PFA coated cable, PEEK isolators and 316L
stainless steel cable weight
Approvals
Dust Ignition Proof:
CE, RCM, ATEX II 1/2 D, 2 D IP6X T100 °C
1)
Intrinsically Safe
CE, RCM, ATEX II 1 G EEx ia IIC T6 ... T4,
ATEX II 1/2 D, 2 D IP6X T100 °C
Flameproof Enclosure with IS Probe:
CE, RCM, ATEX II 1/2 G EEx d[ia] IIC T6 ... T4,
ATEX II 1/2 D T100 °C
1)
Intrinsically Safe
CSA/FM Class I, Div. 1, Groups A, B, C, D
CSA/FM Class II, Div. 1, Groups E, F, G
CSA/FM Class III T4
Explosion Proof Enclosure with IS Probe:
CSA/FM Class I, Div. 1, Groups A, B, C, D
CSA/FM Class II, Div. 1, Groups E, F, G
CSA/FM Class III T4
General Purpose (CSA, FM)
General Purpose (CSA, FM, CE, RCM)
Enclosure and Lid
Aluminum epoxy coated
2 x ½" NPT via adapter - cable inlet, IP65
2 x M20 x 1.5 cable inlet, IP65
2 x ½" NPT via adapter - cable inlet, IP68
2 x M20 x 1.5 cable inlet, IP68
Active shield length
Standard length -
(125 mm threaded, 105 mm flanged)
Extended shield -
(250 mm threaded, 230 mm flanged)
Extended shield -
(400 mm threaded, 380 mm flanged)
1)
Barrier or Intrinsically Safe power supply required for Intrinsically Safe
protection.
2) Available with Probe version options A, B, F ... K, only
[t 1 000 mm (39.7 inch)].
© Siemens AG 2018
Article No.
7ML5661-
-
7 7 7 7 7
7 7 7 7
0
1
0
1
0
1
B
C
D
F
G
H
J
A
B
C
D
0
1
2
2)
Selection and Ordering data
Further designs
Please add "-Z" to Article No. and specify Order
code(s).
Total insertion length: enter the total insertion length
in plain text description
Stainless steel tag [70 x 13 mm (2.75 x 0.5 inch)]:
Measuring-point number/identification
(max. 27 characters) specify in plain text
Manufacturer's test certificate: M to DIN 55350,
Part 18 and to ISO 9000
Material inspection Certificate Type 3.1 per
EN 10204
Operating Instructions
All literature is available to download for free, in a
range of languages, at
http://www.siemens.com/
processinstrumentation/documentation
Accessories
Level Measurement
Point level measurement
RF Capacitance switches
Pointek CLS300 - Digital
Order code
Y01
Y15
C11