Start Up

After Pointek CLS200 is properly mounted apply power to the unit. The green LED (L3)
glows, indicating the unit is powered and operational.
Setpoint Adjustment
switches
P1
delay
L1
sensor
L2
status
output
(yellow)
status
(red)
Use the potentiometers P1 and P2 to adjust the alarm delay and setpoint. Follow the
setup procedure for the application that most closely describes your operation:
Application
General
Demanding
Interface
detection
Calibration for general applications (Failsafe low, no delay)
1.
Ensure the green power LED L3 is on.
2.
Set DIP switches S1 to S4 toOFF.
3.
Set DIP switch S5 ON (set-up mode).
4.
Ensure the probe is uncovered. If the yellow sensor status LED L1 is not on, turn the
trip-point potentiometer P2 counter-clockwise until it just turns on.
5.
Turn the trip-point potentiometer P2 clockwise until LED L1 just turns off.
6.
Set DIP switch S5 to OFF (run mode).
Calibration for demanding applications (Failsafe low, no delay)
1.
Ensure that the green power LED L3 is on.
2.
Set DIP switches S1 to S4 to OFF.
3.
Set DIP switch S5 to ON (set-up mode).
4.
Turn the delay potentiometer P1 fully counterclockwise.
5.
Adjust the material level of the process so that the sensor is immersed.
1.
When S3 is set to ON, it inverts the relay function, and the functioning of S1 and S2.
Page 32
Pointek CLS200/300 Standard – OPERATING INSTRUCTIONS
1
.
P2
trip point
L3
power
(green)
Material
• dry solids
• low viscosity liquids
• hygroscopic / wet solids
• high viscosity and high
conductivity liquids
• liquid A / liquid B
• foam / liquid
O
1 2 3 4 5
F
F
/ROCKER DOWN
Switches shown in OFF position.
Setup conditions
sensor uncovered;
min. 100 mm (4") free space all around
sensor immersed then uncovered; but
retaining max. possible material buildup
immerse sensor in whichever material
has lowest dielectric constant
1
delay: alarm activation
delay: alarm deactivation
1
failsafe/alarm
test delay settings
set-up mode / run
mode
7ML19985JH04