Operation: Pointek CLS200 Standard
model

User Interface

A switch bank of five dip switches allows you to control the settings for Pointek CLS200
(standard model).
Three LEDs (L2, L1, and L3) indicate output status, sensor status, and power ON or
OFF.
Two potentiometers (P1 and P2) adjust the alarm delay and trip point settings. Note:
turning P2 clockwise decreases sensitivity; counter-clockwise increases sensitivity.
switches shown in
OFF position
O
1 2 3 4 5
F
F
/ROCKER DOWN

Indicators

Three LEDs (L1, L2, and L3) indicate power status, sensor status, and alarm output status:
LED
status
sensor contacting, or very close to, process
Lit
material
(material capacitance greater than setpoint for P2)
sensor not contacting process material
Unlit
(material capacitance less than setpoint for P2)
Page 28
Pointek CLS200/300 Standard – OPERATING INSTRUCTIONS
P1
delay
L2
output
status
(red)
Sensor status:
L1 (yellow)
switch bank
L3
L1
sensor
power
status
(green)
(yellow)
Output status:
L2 (red)
alarm OFF
(relay energized/
switch closed)
alarm ON
(relay de-energized/
switch open)
P2
trip point
Power status:
L3 (green)
power
ON
no power
7ML19985JH04