Recommended Cable Entries (equivalents can be
used)
General Purpose Cable Entry: M20 (A5E03252531) and ½" NPT
(A5E03252530)
6 mm (0.24")
M20 x 1.5
1.
Strip cable and expose braided shield.
2.
Feed cable through dome nut and clamping insert. Fold braided shield over clamping
insert. Make sure that braided shield overlaps the O-ring by 3/32" (2 mm) and covers
the entry 360 degrees.
3.
Push clamping insert into body and tighten dome nut. Assemble into housing.
Hazardous Location Cable Entry: M20 (A5E03252528) and ½" NPT
(A5E03252527)
15 mm (0.59")
½" NPT or
M20
(5)
(4)
1.
Strip the cable to suit equipment and expose armour/braid.
2.
Push the cable through the diaphragm shield/armour spigot (4). Pre-fitted cable
guide (4.1) can now be discarded. The diaphragm seal can be rolled back to ease
assembly as required. Spread armour/braid over the diaphragm seal/armour spigot
Page 22
Pointek CLS200/300 Standard – OPERATING INSTRUCTIONS
24 mm
(0.94")
64.4 mm
(2.54")
(3)
(2)
(1)
13 mm (0.51")
½" NPT
(1) Backnut
(2) Middle nut
(3) Reversible armour clamp
(4) Diaphragm seal/Armour spigot
(4.1) Cable guide
(5) Entry (with captive deluge seal)
24 mm
(0.94")
7ML19985JH04