SICK T4000 Multi Instrucciones De Operación página 151

Ocultar thumbs Ver también para T4000 Multi:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Operating instructions
T4000 Multi
8011036/TF94/2010-06-29 © SICK AG • Industrial Safety Systems • Germany • Subject to change without notice
System description
LED
LED OUT
STATE
yellow
green
3 flash-
ing
pulses
with
repeti-
tion after
1 s
4 flash-
ing
pulses
with
repeti-
tion after
1 s
LED DIA
Operational status
red
Teach process failed or
configuration changed
without new teach-in e.g
•24-V-signal on input of
RESET button although
"automatic reset" was
taught
•external device monitoring
activated although no exte-
rnal device monitoring was
taught (e.g. because the
contactors were open dur-
ing the teach-in)
•the DIP switch setting was
changed without a new
teach process
•not all protective doors
which were selected with
the DIP switch were closed
during the teach process
EDM error
Possible causes:
Malfunction on the contactor
monitored,
Actuator not outside the res-
ponse range long enough af-
ter removal from the respon-
se range, as a result the
feedback circuit cannot close
in this short time. Please
note the dropout time for the
contactor monitored.
3
Chapter
151

Publicidad

Tabla de contenido
loading

Tabla de contenido