Description Of Fault Indications - Grundfos LC 221 Manual De Instrucciones

Tabla de contenido

Publicidad

7.4 Description of fault indications

If a fault occurs, the symbol
the 14-segment characters in the display. To see the kind of fault, if it is automatically reset and the code is not longer visible, open the
fault log (see fig. 10). When you leave the fault log, the symbol
The last 20 faults are stored in the fault log as fault codes. The meaning of the fault codes are described in the table below:
Fault
Meaning
code
Phase sequence
F001
failure
F002
One phase missing
F003
High liquid level
Level measurement
F004
failure
Overtemperature,
F005
pump 1
Overtemperature,
F006
pump 2
F007
Overcurrent, pump 1
F008
Overcurrent, pump 2
Operating time
F011
exceeded, pump 1
Operating time
F012
exceeded, pump 2
F013
External fault
F014
Battery failure
Relay or contactor
F015
does not open,
pump 1
Relay or contactor
F016
does not close,
pump 1
Relay or contactor
F017
does not open,
pump 2
Relay or contactor
F018
does not close,
pump 2
Communication
F019
failure
Internal float switch
F020
high level
Communication
F117
failure
will be visible, an audible alarm will be given by the buzzer and the fault code will be written by means of
Reset of
fault
Displayed
Flashing
indications Description
text
symbols
Auto Man
F001
F002
F003
SENSOR
-
TEMP
TEMP
F007
F008
F011
F012
EXTERN
-
BAT
-
RELAY
RELAY
RELAY
RELAY
-
-
F020
F117
-
will disappear.
(Only three-phase pumps)
The phase sequence between control board and power supply is
wrong.
(Only three-phase pumps)
One phase is missing.
The liquid level is high in relation to preset value.
Sensor signal out of range or lost.
Motor thermal switches connected to the controller will stop
pump 1 in case of overheating.
Motor thermal switches connected to the controller will stop
pump 2 in case of overheating.
Pump 1 is stopped if an overcurrent is measured for a certain
period of time (blockage protection).
Pump 2 is stopped if an overcurrent is measured for a certain
period of time (blockage protection).
Pump 1 is stopped if normal operating time of the pump is
exceeded, e.g. due to venting problems of pump housing, closed
discharge valve (forgotten to open it after service/maintenance),
forgotten to switch back to automatic mode, if ON-OFF-AUTO
switch is set to "ON" for service/maintenance. A subsequent
emergency operation starts and stops the pump automatically
until the controller gets a regular stop signal from the sensor.
The controller then switches back to normal operation.
Pump 2 is stopped if normal operating time of the pump is
exceeded, e.g. due to venting problems of pump housing, closed
discharge valve (forgotten to open it after service/maintenance),
forgotten to switch back to automatic mode, if ON-OFF-AUTO
switch is set to "ON" for service/maintenance. A subsequent
emergency operation starts and stops the pump automatically
until the controller gets a regular stop signal from the sensor.
The controller then switches back to normal operation.
An external level switch can be connected to the controller to
give an alarm when basement outside the lifting station is
flooded by groundwater or water from burst water pipe.
The battery is empty and must be replaced.
Pump 1 receives a signal to stop, but does not react.
This situation is detected by current measurement.
Pump 1 receives a signal to start, but does not react.
This situation is detected by current measurement.
Pump 2 receives a signal to stop, but does not react.
This situation is detected by current measurement.
Pump 2 receives a signal to start, but does not react.
This situation is detected by current measurement.
The main board has detected a bad connection to the display.
Call service.
The optional float switch inside the tank is switched.
The tank is probably flooded.
The display cannot communicate with the main board.
Call service.
17

Publicidad

Tabla de contenido
loading

Tabla de contenido