Descargar Imprimir esta página

RS Pro RS-33S Manual De Instrucciones página 10

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Battery Capacity Tester / EN
Power source: Meter→ six AA size 1.5V alkaline batteries.
Maximum power consumption : 1.0VA
Continuous operating time : 5.5 hours approx.
Maximum altitude : 2000m or less.
Size : Meter→ H198 × D49 × W94mm
DCA current adaptor → H193 × D31 × W69mm
Weight : Meter → 530g approx. (including batteries)
DCA current adaptor → 240g approx. (including batteries)
Accessories : Clip – type test lead with temperature sensor, Probe – type test lead,
3-2 Electrical Specifications
Conditions to guarantee accuracy :
Temperature : 23°C ± 5°C
Humidity : 80%RH or less (non condensing).
Temperature coefficient : 0.10 x (specified accuracy) / °C. (<18°C or > 28°C)
Zero adjustment : After zero adjustment for each range.
Resistance measurement
Range
4mΩ
40mΩ
400mΩ
40Ω
400Ω
Measuring current frequency : 1kHz ± 30Hz
7
DCA current adaptor→ one 9V PP3 battery.
DCA current adaptor, Zero adjustment board, Instruction manual,
batteries, AC adaptor, USB cable, CD PC software, Carrying case.
Resolution
1µΩ
10µΩ
100µΩ
1mΩ
10mΩ
100mΩ
Measurement current
40mA approx.
40mA approx.
4mA approx.
400µA approx.
40mA approx.
4µA approx.
Accuracy
±(3% reading ±
20 digits)
±(0.8% reading ±
6 digits)
09/15/17 Version No. 00

Publicidad

loading

Este manual también es adecuado para:

146-6430