8. Configuration via display and operating unit
1. Open the operating menu with [↵].
Select "Basic setting" and confirm with [↵].
2. Select "Scale setting" and confirm with [↵].
3. Select "Wet adjustm." and confirm with [↵].
EN
4. Define the current measured value as start of measuring
range or end of measuring range:
To define as start of measuring range:
Confirm "min. adjustm." with [↵].
To define as end of measuring range:
Confirm "max. adjustm." with [↵].
5. Change digit using [▲] [▼] and confirm with [↵]. The cursor
moves to the next digit. Repeat for each digit. When the last
digit is exited, the menu moves back to step 2.
8.3.2 Performing a dry adjustment
Via the dry adjustment, the values for the start of the measuring range and the end of the
measuring range are entered manually. The respective output signal can be adjusted.
Requirement
Setting range
30
With the input of current values that are not
either 4 mA or 20 mA the pressure value is
converted into the standardised current signals
as soon as the current value entered is accept-
ed.
Process transmitter does not have to be installed.
No measurement is running. If there is a running measurement, the
output signal can alter abruptly.
Start of measuring range: -10 ... +110 % of measuring range
End of measuring range: 1 ... 120 % of measuring range
Max. turndown: 100 : 1 (recommended max. 4 : 1)
WIKA operating instructions, model DMSU22SA