8. Configuration via display and operating unit
8. Configuration via display and operating unit
8.1 Configuring pressure measurement
1. Open the operating menu with [↵].
Select "Basic setting" and confirm with [↵].
EN
2. Select "Application" and confirm with [↵].
3. Select "Pressure" and confirm with [↵].
4. Select "Unit" and confirm with [↵].
5. Select pressure unit and confirm with [↵].
Pressure unit is set.
6. Go back one menu level using [ESC].
Select "Mode" and confirm with [↵].
7. Select "Pressure" and confirm with [↵].
» Mode is set.
8. Scale the measuring range.
→ See chapter 8.6 "Scaling the measuring range"
9. Perform a mounting correction.
→ See chapter 8.8 "Mounting correction (offset)".
» Pressure measurement is configured.
Level and volume modes cannot be used for this instrument.
28
WIKA operating instructions, model DMSU22SA