Descargar Imprimir esta página

WIKA DMSU22SA Manual De Instrucciones página 43

Publicidad

Idiomas disponibles

Idiomas disponibles

10. Detailed settings / 11. Instrument information
10.8.2 Alarm signal via HART
The instrument status will be set to "Diaphragm rupture".
10.8.3 Alarm signal via current loop
The output residual current can be set to 2 values
3.5 mA = alarm signal downscale
21.5 mA = alarm signal upscale
The factory setting is 3.5 mA.
See chapter 10.3 "Setting the alarm signal" to change the customer-specific presetting.
11. Instrument information
11.1 Displaying measuring range
1. Open the operating menu with [↵].
Select "Info" and confirm with [↵].
2. Select "Measuring range" and confirm with [↵].
» Measuring range is displayed.
WIKA operating instructions, model DMSU22SA
communication
EN
43

Publicidad

loading