8. Configuration via display and operating unit
8.5.2 Performing a dry adjustment
The mounting correction is registered manually via the dry adjustment. For all future
measurements, the mounting correction will be subtracted.
Requirement:
Deviation ≤ 20 % of the measuring range.
1. Open the operating menu with [↵].
Select "Basic setting" and confirm with [↵].
2. Select "Application" and confirm with [↵].
3. Select "Pressure" and confirm with [↵].
4. Select "Mounting corr." and confirm with [↵].
5. Select "Change" and confirm with [↵].
6. Change digit using [▲] [▼] and confirm with [↵]. The cursor
moves to the next digit. Repeat for each digit.
» Entered value will be used as the new zero point.
8.6 Setting the damping
The damping prevents the fluctuation of the output signal when there are short-term
fluctuations in the measured value. Safety shut-downs due to turbulent processes are
thus prevented.
Pressure spikes will still be registered, e.g. as P
"Diagnostic".
Setting range
0 ... 99.9 s
1. Open the operating menu with [↵].
Select "Basic setting" and confirm with [↵].
WIKA operating instructions, model DMSU22SA
in the menu point
max
EN
33