7.1 General data

Ambient and operating conditions
Permissible ambient temperature:
0 °C to +55 °C.
Permissible air humidity: max. relative humidity:
70 % at 40 °C, 90 % at 35 °C.
Housing
Materials:
– Housing: Die-cast zinc
– Hood: Corrosion-resistant die-cast aluminium,
painted with a silicone-free structured lacquer
Colour: Black
Degree of protection in acc. with DIN EN 60529:
IP65
Power supply
220-240 V ± 10 %, 50/60 Hz ± 5 %, 100 % on
time (standard)
110-120 V ± 10 %, 50/60 Hz ± 5 %
24 VAC ± 10 %, 50/60 Hz ± 5 %
Insulation class B in acc. with VDE 0530
Adjustment angle
270 °
Power consumption
Max. 2 VA
Actuating time
90 seconds (50 Hz), 75 seconds (60 Hz) for DMH
pumps
> 90 seconds for DMX 221 and DMX 226 pumps.
The exact actuating time cannot be specified for
DMX pumps, as it will depend on the technical
properties of the pump in question.
Weight
Approximately 2.6 kg
10
7.1.1 Servomotor with reversing potentiometer
Control variant
Open/close signal
Reversing potentiometer 1 kΩ
7.1.2 Servomotor with analogue control
Control variant
Analogue control
Input/output
– 4-20 mA (standard setting)
– 0-20 mA (switchable)
With service switch for manual adjustments
Setpoint input
4 (0) - 20 mA (DC)
Load 250 Ω
Overload protection 25 mA
Protection against reverse polarity to -25 mA
ESD protection, input filter
Resolution: 10 bits
Actual value output
Fixed limits: 0-20 mA or 4-20 mA
Current sink: Max. load 500 Ω
Resolution: 10 bits
Service switch
Max. switching capacity 10(3) A, 250 VAC