Criteria for yield calculations:
Location:
Unobstructed sunlight throughout the year
Orientation:
Solar modules facing south (locations in northern hemisphere)
Tilt angle:
Of solar modules (ideal tilt angle in winter: 60°)
Shading:
Consideration of shading caused by buildings or trees in future
Season:
The solar systems have been calculated for the season with the poorest weather (winter). Du-
ring this time, the solar panels only provide around 1/4 of the daily yield that they provide in the
summer months.
Example 1: Germany (Hanover)
Maximum connected load in winter at constant load and with a power reserve amounting to
approximately five days:
...-12-10
*
160 mW
* Solar modules facing south, 60° tilt angle, year-round operation
Example 2: Spain (Madrid)
Maximum connected load in winter at constant load and with a power reserve amounting to
approximately five days:
...-12-10
*
250 mW
* Solar modules facing south, 60° tilt angle, year-round operation
RAD-SOL-SET-...
...-24-100
*
2.5 W
RAD-SOL-SET-...
...-24-100
*
3.8 W
...-24-200
*
5 W
...-24-200
*
8.5 W
7150_ia_05