9.1 Protection against electric shock, indirect contact

WARNING
Electric shock
Death or serious personal injury
- Connect the motor to ground and provide
protection against indirect contact in accordance
with local regulations.
Ground conductors must always have a yellow and green, PE, or
yellow, green and blue, PEN, color marking.
9.1.1 Protection against mains voltage transients
The motor is protected against mains voltage transients in
accordance with EN 61800-3.
9.1.2 Motor protection
The motor requires no external motor protection. The motor
incorporates thermal protection against slow overloading and
blocking.

9.2 Cable requirements

9.2.1 Cable cross-section
DANGER
Electric shock
Death or serious personal injury
- Always comply with local regulations as to cable
cross-sections.
1 x 200-230 V
Power
Conductor
[hp (kW)]
type
Solid
0.33 - 3.0
(0.25 - 2.2)
Stranded
3 x 440-480 V
Power
Conductor
[hp (kW)]
type
Solid
0.33 - 3.0
(0.25 - 2.2)
Stranded
Solid
4.0 - 15
(3.0 - 11)
Stranded
3 x 200-240 V
Power
Conductor
[hp (kW)]
type
Solid
1.5 - 2.0
(1.1 - 1.5)
Stranded
Solid
3.0 - 7.5
(2.2 - 5.5)
Stranded
9.2.2 Conductors
Type
Stranded or solid copper conductors.
Temperature rating
Temperature rating for conductor insulation: 140 °F (60 °C).
Temperature rating for outer cable sheath: 167 °F (75 °C).
14
Cross section
2
[mm
]
[AWG]
1.5 - 2.5
16-12
1.5 - 2.5
16-12
Cross section
2
[mm
]
[AWG]
1.5 - 10
16-8
1.5 - 10
16-8
2.5 - 10
14-8
2.5 - 10
14-8
Cross section
2
[mm
]
[AWG]
1.5 - 10
16-8
1.5 - 10
16-8
2.5 - 10
14-8
2.5 - 10
14-8

9.3 Mains supply

DANGER
Electric shock
Death or serious personal injury
- Use the recommended fuse size. See sections
31.1 Supply voltage
9.3.1 Single-phase supply voltage
1 x 200-240 V - 10 %/+ 10 %, 60 Hz, PE.
Check that the supply voltage and frequency correspond to the
values stated on the nameplate.
If you want to supply the motor through an IT
network, make sure that you have a suitable motor
variant. If you are in doubt, contact Grundfos.
The wires in the motor terminal box must be as short as possible.
Except from this is the separated grounding conductor which
must be so long that it is the last one to be disconnected in case
the cable is inadvertently pulled out of the cable entry.
For maximum feeder overcurrent protective device (FOPD)
ratings, see section
31.1 Supply
L1
FOPD
L2
PE
Installation in building Breaker cabinet
Fig. 15 Example of a mains-connected motor with feeder
overcurrent protective device
Fig. 16 Power supply connection, single-phase motors
and
32.1 Supply
voltage.
voltage.