Possible functions, digital input/output 4
Function if input
See details in section
17.13 Digital inputs
• Not active
• External stop
• Min.
• Max.
• "User-defined speed"
• External fault
• Alarm resetting
• Dry running
• Accumulated flow*
• "Predefined setpoint digit
3"
• "Activate output"
• "Local motor stop"
17.15 Activation delay
Pump variant
TPE3, TPE3 D
TPE2, TPE2 D
Select the activation delay, T1.
It is the time between the digital signal and the activation of the
selected function.
Range: 0 to 6000 seconds.
Duration timer mode
Select the mode. See fig. 58.
•
Not active
•
active with interrupt, mode A
•
active without interrupt, mode B
•
active with after-run, mode C.
Select the duration time, T2.
It is the time which, together with the mode, determines how long
the selected function is active.
Range: 0 to 15,000 seconds.
T input > T1 + T2
T input > T1 + T2
Digital input
T input
Mode A
T1
T2
Mode B
T1
T2
Mode C
T1
Fig. 58 Duration timer function of digital inputs
Factory setting
See section
35. Factory
settings.
42
Function if output
See details in section
17.16 "Signal relay 1 and 2"
(Relay outputs)
• Not active
• Ready
• Alarm
• Operation
• Pump running
• Warning
• Limit 1 exceeded
• Limit 2 exceeded
• Digital input 1, state
• Digital input 2, state
• Digital input 3, state
• Digital input 4, state
Activation delay
-
●
T input < T1 + T2
T input < T1 + T2
T input
T1
T1
T2
T2
T1
T2
17.16 "Signal relay 1 and 2" (Relay outputs)
Pump variant
TPE3, TPE3 D
TPE2, TPE2 D
Function
Relay output 1
Relay output 2
* See section
9.5.1 Connection terminals, advanced functional
module, FM
300.
The pump incorporates two signal relays for potential-free
signalling. For further information, see section
Function
You can configure the signal relays to be activated by one of the
following incidents:
•
Not active.
•
Ready
The pump can be running or is ready to run and no alarms are
present.
•
Alarm
There is an active alarm and the pump is stopped.
•
"Operating" (Operation)
"Operating" equals "Running" but the pump is still in operation
when it has been stopped due to a warning.
•
"Running" (Pump running)
•
Warning
There is an active warning.
•
Digital input 1, state
Follows digital input 1. If digital input 1 is activated, output is
also activated.
•
Digital input 2, state
Follows digital input 2. If digital input 2 is activated, output is
also activated.
•
Digital input 3, state
Follows digital input 3. If digital input 3 is activated, output is
also activated.
•
Digital input 4, state
Follows digital input 4. If digital input 4 is activated, output is
also activated.
•
Limit 1 exceeded
When the Limit 1 exceeded function is activated, the signal
relay is activated. See section
•
Limit 2 exceeded
When the Limit 2 exceeded function is activated, the signal
relay is activated. See section
•
Relubricate
•
External fan control (Control of external fan)
When you select "External fan control", the relay is activated if
the internal temperature of the motor electronics reach a
preset limit value.
Factory setting
See section
35. Factory
settings.
"Signal relays 1 and 2"
●
●
Terminal*
NC, C1, NO
NC, C2, NO
22. Signal
relays.
17.23 Limit-exceeded
function.
17.23 Limit-exceeded
function.