Alarm Relay - Grundfos Conex DIA-G Instrucciones De Instalación Y Funcionamiento

Ocultar thumbs Ver también para Conex DIA-G:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 106
Measured value: Display example of measured
value, Sensor 1.
Sensor 1
xx.xx ppm
xxxx nA
xxxx.x nA/ppm
The following data is displayed:
xx.xx ppm = Current measured value in ppm
xxxx nA = Current input current in nA or µA
xxxx.x nA/ppm = Sensor sensitivity in nA/ppm or
µA/ppm.
Auto test: The current set test interval and the
remaining time until the next sensor test is displayed.
This menu only appears if the automatic function has
been selected in the main menu under "Sensor 1" or
"Sensor 2".
Aut. test S1
Interval
xx.x day
Next test
xx.x day
Interval: Displays the preset test interval. See
also
11.9.1 Sensor
test.
Next test: Displays the remaining time in days
and hours until the next automatic test function.
Sensor data: Sensor-specific data is displayed.
The replacement date is displayed according to the
calibration date (EPROM) and installation date
(detection of new sensor). See section
11.9.4 Replacing/changing a
Sensor data
Sensor
Slope
... µA/ppm
Assembly
... dd.mm.yyyy
Change
... dd.mm.yyyy
For amperometric sensors, this data only
Note
updates when the "New sensor" menu
item is selected.
46
sensor.
Settings: The settings for limit values and the alarm
relay are displayed here so that the values can be
checked without accessing the relevant menus in the
"Setup" menu.
Display examples:
Limit values
LV 1
0.50 ppm
LV 2
1.80 ppm
Fail safe
N.O.
Conf.
No
Delay
30 sec
Hyst.
0.02 ppm

Alarm relay

Test sensor
Limit value 2
Fail safe
N.O.
Delay
30 sec
Conf.
Yes
Test current (check operation of the current
outputs)
Depending on the configuration of the current loops,
the current outputs can be switched on with the
following current values, and the current value can
be output to the system:
Selection of 0, 10, 20 mA when standard range
0-20 mA is selected
Selection of 4, 12, 20 mA when standard range
4-20 mA is selected or for freely configured
current loops
1. Access the "Test current" menu by pressing [OK].
2. Access "Current output 1" for sensor 1 or
"Current output 2" for sensor 2 by pressing [OK].
3. Press the [Up] or [Down] button to select the
current values.
4. Select the row, and press [OK] to set the status of
the current output with the relevant value to "On".
5. Select another row, and press [OK] to switch off
the previous current value and set the new
current value to "On".
6. For every current value, use a suitable measuring
device to check that current is present at the
relevant current output.
– If the relevant current value is present:
Function is OK.
– If the relevant current value is not present: The
current output is faulty.
7. Press [Esc] to exit the test menu. When you exit
the menu, the latest current values for the
sensors are output to the system again.

Publicidad

Tabla de contenido
loading

Tabla de contenido