Connection Of Sensors - Grundfos Conex DIA-G Instrucciones De Instalación Y Funcionamiento

Ocultar thumbs Ver también para Conex DIA-G:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 106

10.7 Connection of sensors

Connect the screening to screen ground
Caution
on one side only!
10.7.1 Amperometric sensors
Connection via 2-wire cable 0.5 mm
screen. Maximum length (maximum distance
between the sensor disc and gas warning controller):
100 metres.
Cables for amperometric gas sensors
Description
Connection cable for
amperometric gas sensors,
10 metres
Connection cable for
amperometric gas sensors,
20 metres
Connection cable for
amperometric gas sensors,
50 metres
sensor 1
45 47
49
sensor 2
46 48
50
Fig. 11
Connection of amperometric sensor
Assignment
-
Sensor 1
+
-
Sensor 2
+
The wire colours refer to Grundfos cable.
Sensor 1:
Connect the brown wire (+) to terminal 49.
Connect the white wire (-) to terminal 45.
Connect the screen to terminal 47.
Sensor 2:
Connect the brown wire (+) to terminal 50.
Connect the white wire (-) to terminal 46.
Connect the screen to terminal 48.
24
2
with single
Product number
96725670
(321-130/10)
96725672
(321-130/20)
96725673
(321-130/50)
Terminal
Wire
45
white
47
screen
49
brown
46
white
48
screen
50
brown

Publicidad

Tabla de contenido
loading

Tabla de contenido