Setting Photocell Mode During Gate Closing (Ft1) - Roger Technology EDGE1/BOX Instrucciones Y Advertencias Para El Instalador

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 158
Medium motor torque. Recommended setting for adjusting force settings correctly.
= minimum obstacle impact force ...
= maximum obstacle impact force.
Maximum motor torque. May only be used if the gate is equipped with a sensing edge.
Setting motor torque MOTOR 2
Increasing or decreasing the value of the parameter increases or decreases motor torque and, as a result, adjusts
obstacle detection sensitivity.
Use values below
SOLO ONLY for particularly lightweight installations not exposed to severe weather conditions
(strong winds or very cold temperatures).
(reduced motor torque = increased sensitivity).
05= 0%.
06= +8%; 07= +16%; 08= +25%; 09= +35% (increased motor torque = reduced sensitivity).
The torque is set with parameter
.
Setting start acceleration MOTOR 1 during opening and closing
Setting start acceleration MOTOR 2 during opening and closing
01= the gate accelerates rapidly at start of manoeuvre ... 10= the gate accelerates slowly and progressively at start of
manoeuvre.
Enable electric lock release reverse impulse
Disabled.
Enabled. The controller applies a brief closing force (max. 4 s) to release the electric lock.
Setting opening speed (%)
Setting closing speed (%)
01= 60% minimum speed ... 05= 100% maximum speed.
Parameters visible ONLY if:
SMARTY5 o 7
SMARTY7R
SMARTY5R5
SMARTY4/HS
PARAMETER
BE20/400
BR20/400/R
ONLY IF
= SMARTY/EMA ENABLED
Opening approach distance setting MOTOR1
Opening approach distance setting MOTOR2
Closing approach distance setting MOTOR1
Closing approach distance setting MOTOR2
from min.
to max.
of turns performed by the motor at the minimum speed. Speed is setted by the control unit
automatically and it isn't adjustable.
Setting number of automatic closure attempts after activation of sensing edge or
obstacle detection (crush protection)
No automatic closure attempts.
From 1 to 3 automatic closure attempts. We recommend setting a value equal to or lower than the value set for param
eter
. Automatic closure is only performed if the gate is completely open.
Setting photocell mode during gate opening (FT1)
DISABLED. Photocell is not active or not installed.
STOP. The gate stops and remains stationary until the next command is received.
IMMEDIATE REVERSE. The gate reverses immediately if the photocell is activated during gate opening.
TEMPORARY STOP. The gate stops as long as the photocell is obstructed. The gate resumed opening when the photocell
is cleared.
DELAYED REVERSE. The gate stops if the photocell is obstructed. The gate closes when the photocell is cleared.

Setting photocell mode during gate closing (FT1)

72