Enable "operator present" function.
N.B.: this parameter is not visible if the value of parameter
Disabled.
Enabled. The open (AP) or close (CH) button must be pressed continuously to operate the barrier. The boom
stops when the button is released.
Barrier open/photocell test function and battery saving mode indicator lamp
N.B.: This parameter is not visible if the value of parameter
The indicator is off when the barrier is closed, and steadily lit during manoeuvres and when the barrier is
open.
The indicator flashes slowly during opening manoeuvres, and is lit steadily when the barrier is completely
open. Flashing rapidly during closing manoeuvres.
If the barrier is stopped in an intermediate position, the lamp extinguishes twice every 15 seconds.
Set to
if the output SC is used for the photocell test. See fig. 5.
Set to
if the output SC is used for the "battery saving" function. See fig. 6.
When the barrier is completely open or closed, the controller unit deactivates any accessories connected to
terminal SC to reduce battery consumption.
N.B.: this parameter is not visible if the value of parameter
Set to
if the output SC is used for the "battery saving" function and photocell test function. See fig. 6.
N.B.: this parameter is not visible if the value of parameter
Enable B73/EXP signal device to indicate barrier completely open/closed
positions (NC potential-free contact)
Disabled.
Enabled.
When the boom is completely open, contact TO (NC) opens and the green LED illuminates on the B73/
EXP board.
When the boom is completely closed, contact TC (NC) opens and the red LED illuminates on the B73/EXP
board.
"BreakAway" ACS/BA/60 shatter-proof system enabling (fig. 8)
Connect the shatter-proof system sensor to one of the control inputs on the control unit.
When the shatter-proof system is triggered, the signal switches from N.C. to N.O.
If NOT connected, all control inputs will have standard function.
Connected on AP input
Connected on CH input
Connected on PP input
Connected on PED input
Connected on ORO input
SC output operating mode (fig. 9)
By connecting a Relay to the SC output, an error alert contact can be achieved at an external control system.
STANDARD operation managed by parameter
With the indicator lamp connected to the SC output and if lit, it indicates that the shatter-proof system sensor
ACS/BA/60 is in stand-by. Indicator light off due to an anomaly: sensor alarm.
With the indicator lamp connected to the SC output and if lit, it indicates that the barrier is powered by the
mains source or by a charged battery.
Indicator light off due to an anomaly: the battery is exhausted (voltage level set via parameter
With the indicator lamp connected to the SC output and if lit, it indicates that none of the abnormal situations
1 or 2 occurred.
With the indicator lamp off it indicates that at least one of the abnormal situations 1 or 2 has occurred.

Setting automatic closing time

The timer starts from the barrier open state and continues for the set time. Once the set time is reached,
the barrier closes automatically. The timer count restarts if a photocell is triggered.
pause time settable from 00 to 90 s.
pause time settable from 2 to 9 min.
68
=
,
or
.
is different from
.
=
,
or
.
=
,
or
.
).