Descargar Imprimir esta página

Grundfos MGE motors Serie Instrucciones De Instalación Y Funcionamiento página 18

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 209
two digital inputs or one digital input and one open-collector output
GENIbus connection.
The inputs and outputs are internally separated from the mains-conducting parts by reinforced insulation and galvanically separated from other
circuits. All control terminals are supplied with protective extra-low voltage (PELV), ensuring protection against electric shock.
Connection terminals for the mains supply
Phases
Single-phase
Three-phase
Connection terminals for inputs and outputs
DANGER
Electric shock
Death or serious personal injury
Make sure that the wires to be connected to the connection groups below are separated from each other by reinforced insulation
in their entire lengths.
Terminal Type
Function
Digital input/output, configurable.
10
DI3/OC1
Open collector: Maximum 24 V resistive or inductive.
Analog input:
4
AI1
0.5 - 3.5 V, 0-5 V or 0-10 V.
Digital input, configurable.
2
DI1
5
+5 V
Power supply to a potentiometer or sensor.
6
GND
Protective earth.
A
GENIbus, A GENIbus, A (+).
Y
GENIbus, Y GENIbus, Y (GND).
B
GENIbus, B GENIbus, B (-).
Related information
4.2.4 Connecting an external switch
4.2.7.2 Standard functional module, FM 200
Inputs and outputs
The module has these connections:
two analog inputs
two digital inputs or one digital input and one open-collector output
Grundfos Digital Sensor input and output
two signal relay outputs
GENIbus connection.
The inputs and outputs are internally separated from the mains-conducting parts by reinforced insulation and galvanically separated from other
circuits. All control terminals are supplied with protective extra-low voltage (PELV), ensuring protection against electric shock.
Signal relay 1
LIVE: You can connect supply voltages up to 250 VAC to the output.
PELV: The output is galvanically separated from other circuits. Therefore, you can connect the supply voltage or protective extra-low voltage to
the output as desired.
18
OC
+24 V*
+24 V*/5 V*
Digital input 1 is factory-set to be start or stop input where an open circuit results in stop. A jumper has been
factory-fitted between terminals 2 and 6. Remove the jumper if digital input 1 is to be used as external start
or stop or any other external function.
Terminals
N, PE, L
L1, L2, L3, PE
DI
GND
10
DI3/OC1
4
AI1
2
DI1
+
+
5
+5 V
6
GND
A
GENIbus A
Y
GENIbus Y
B
GENIbus B

Publicidad

loading