16. Press the Right button to continue.
17. Select Bus as the communication method to be used between the two motors.
18. Press the Right button to continue.
19. Select pump 2 (motor 2).
20. Select the additional motor from the list.
Use OK or the Radio communication button to identify the pump.
21. Press the Right button to continue.
22. Confirm the setting by pressing Send.
23. When you have finished the setup and the dialog box disappears, wait for the green indicator light in the middle of Grundfos Eye to light
up.
6.46.4.3 Setting a multipump or multimotor system with the advanced operating panel and a wireless motor connection
1. Power on both motors.
2. On both motors, set the analog and digital inputs according to the connected equipment and the required functionality. See
setup"
.
3. Select the Assist menu on one of the motors and Setup of multi-pump system (setup of multimotor system).
4. Press the Right button to continue.
5. Select Wireless as the communication method to be used between the two motors.
6. Press the Right button to continue.
7. Select the desired multimotor function. See
8. Press the Right button three times to continue.
9. Press OK to search for other motors.
The green indicator light in the middle of Grundfos Eye flashes on the other motors.
10. Press OK or the Radio communication button on the motor which is to be added to the multimotor system.
11. Press the Right button to continue.
12. Set Time for pump changeover.
This is the time at which the alternation between the two motors is to take place.
This step applies only if you have selected Alternating operation, time and if the motors are fitted with FM 300.
13. Press the Right button to continue.
14. Press OK to confirm the setting.
The multipump or multimotor function icons appear at the bottom of the operating panels.
6.46.4.4 Setting a multipump or multimotor system with the advanced operating panel and a wired motor connection
1. Connect the two motors with each other with a 3-core screened cable between the GENIbus terminals A, Y, B.
2. Set the needed analog and digital inputs according to the connected equipment and the required functionality. See
3. Assign motor number 1 to the first motor. See
4. Assign motor number 2 to the other motor.
5. Select the Assist menu on one of the motors and Setup of multi-pump system.
6. Press the Right button to continue.
7. Select Wired GENIbus as the communication method to be used between the two motors.
8. Press the Right button twice to continue.
9. Select the desired multimotor function. See
10. Press the Right button to continue.
11. Press OK to search for other motors.
12. Select the additional motor from the list.
13. Press the Right button to continue.
14. Set Time for pump changeover.
This is the time at which the alternation between the two motors is to take place.
This step applies only if you have selected Alternating operation, time and if the motors are fitted with FM 300.
Multipump or multimotor
function.
"Number" ("Pump
number").
Multipump or multimotor
function.
"Assisted pump
"Assisted pump setup"
.
59