Descargar Imprimir esta página

Grundfos MGE motors Serie Instrucciones De Instalación Y Funcionamiento página 58

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 209
Advanced operating panel and wireless motor connection.
Advanced operating panel and wired motor connection.
6.46.4.1 Setting a multipump or multimotor system with Grundfos GO Remote and a wireless motor connection
1. Power on both motors.
2. Establish contact to one of the motors with Grundfos GO Remote.
3. Set the needed analog and digital inputs via Grundfos GO Remote according to the connected equipment and the required functionality.
See
"Assisted pump setup"
.
4. Assign a name to the motor using Grundfos GO Remote. See
5. Disconnect Grundfos GO Remote from the motor.
6. Establish contact to the other motor.
7. Set the needed analog and digital inputs via Grundfos GO Remote according to the connected equipment and the required functionality.
See
"Assisted pump setup"
.
8. Assign a name to the motor using Grundfos GO Remote. See
9. Select the Assist menu and Setup of multi-pump system.
10. Select the desired multimotor function. See
11. Press the Right button to continue.
12. Set the time at which the alternation between the two motors is to take place.
This step applies only if you have selected Alternating operation, time and if the motors are fitted with FM 300.
13. Press the Right button to continue.
14. Select Radio as the communication method to be used between the two motors.
15. Press the Right button to continue.
16. Select pump 2 (motor 2).
17. Select the pump from the list.
Use OK or the Radio communication button to identify the pump.
18. Press the Right button to continue.
19. Confirm the setting by pressing Send.
20. When you have finished the setup and the dialog box disappears, wait for the green indicator light in the middle of Grundfos Eye to light
up.
6.46.4.2 Setting a multipump or multimotor system with Grundfos GO Remote and a wired motor connection
1. Connect the two motors with each other with a 3-core screened cable between the GENIbus terminals A, Y, B.
2. Power on both motors.
3. Establish contact to one of the motors with Grundfos GO Remote.
4. Set the required analog and digital inputs via Grundfos GO Remote according to the connected equipment and the required functionality.
See
"Assisted pump setup"
.
5. Assign a name to the motor using Grundfos GO Remote. See
6. Assign motor number 1 to the motor. See
7. Disconnect Grundfos GO Remote from the motor.
8. Establish contact to the other motor.
9. Set the analog and digital inputs according to the connected equipment and the required functionality by means of Grundfos GO Remote.
See
"Assisted pump setup"
.
10. Assign a name to the motor using Grundfos GO Remote. See
11. Assign motor number 2 to the motor. See
12. Select the Assist menu and Setup of multi-pump system (multimotor setup).
13. Select the desired multimotor function. See
14. Press the Right button to continue.
15. Set the time at which the alternation between the two motors is to take place.
This step applies only if you have selected Alternating operation, time and if the motors are fitted with FM 300.
58
"Pump name" ("Motor
"Pump name" ("Motor
Multipump or multimotor
function.
"Pump name" ("Motor
"Number" ("Pump
number").
"Pump name" ("Motor
"Number" ("Pump
number").
Multipump or multimotor
function.
name").
name").
name").
name").

Publicidad