Signal relay 2
PELV: The output is galvanically separated from other circuits. Therefore, you can connect the supply voltage or protective extra-low voltage to
the output as desired.
Connection terminals for the mains supply
Phases
Single-phase
Three-phase
Connection terminals for inputs and outputs
DANGER
Electric shock
Death or serious personal injury
‐
Make sure that the wires to be connected to the connection groups below are separated from each other by reinforced insulation
in their entire lengths.
Terminal Type
NC
Normally closed contact
C1
Common
NO
Normally open contact
NC
Normally closed contact
C2
Common
NO
Normally open contact
10
DI3/OC1
4
AI1
2
DI1
5
+5 V
6
GND
A
GENIbus, A
Y
GENIbus, Y
B
GENIbus, B
3
GND
15
+24 V
8
+24 V
26
+5 V
OC
GND
+24 V*
+24 V*
+24 V*
+24 V*/5 V*
+
+24 V*
+24 V*
+24 V*/5 V*
Function
Signal relay 1. LIVE or PELV.
Signal relay 2. PELV only.
Digital input/output, configurable.
Open collector: Maximum 24 V resistive or inductive.
Analog input:
0-20 mA or 4-20 mA
0.5 - 3.5 V, 0-5 V or 0-10 V.
Digital input, configurable.
Digital input 1 is factory-set to be start or stop input where an open circuit results in stop. A
jumper has been factory-fitted between terminals 2 and 6. Remove the jumper if digital input 1
is to be used as external start or stop or any other external function.
Power supply to a potentiometer or sensor.
Protective earth.
GENIbus, A (+).
GENIbus, Y (GND).
GENIbus, B (-).
Protective earth.
Power supply.
Power supply.
Power supply to a potentiometer or sensor.
Terminals
N, PE, L
L1, L2, L3, PE
NC
C1
NO
NC
C2
NO
DI
10
DI3/OC1
4
AI1
2
DI1
+
5
+5 V
6
GND
A
GENIbus A
Y
GENIbus Y
B
GENIbus B
3
GND
15
+24 V
8
+24 V
26
+5 V
23
GND
25
GDS TX
24
GDS RX
+5 V*
7
AI2
19