6.50 Factory settings for Grundfos GO Remote
Settings
Setpoint
Operating mode
Set user-defined speed
Control mode
Buttons on product
Controller
Operating range
Ramps
Number
Radio communication
Analog input 1
Analog input 2
Analog input 3
Pt100/1000 input 1
Pt100/1000 input 2
Digital input 1
Digital input 2
Digital input/output 3
Digital input/output 4
Predefined setpoint
Analog output
External setpoint funct.
Signal relay 1
Signal relay 2
Limit 1 exceeded
Limit 2 exceeded
Standstill heating
Motor bearing monitoring
7. Service
DANGER
Electric shock
Death or serious personal injury
‐
Switch off the power supply to the product including the power supply for the signal relays. Wait at least 5 minutes before you
make any connections in the terminal box. Make sure that the power supply cannot be switched on accidentally.
DANGER
Magnetic field
Death or serious personal injury
‐
Do not handle the motor or rotor if you have a pacemaker.
If service of the product is required, contact Grundfos.
7.1 Insulation resistance test
Do not use a megger or similar high voltage instrument, as the built-in electronics may be damaged.
MGE
67 %
Normal
67 %
Constant curve
Active
Kp: 0.5
Ti: 0.5
25-100 %
Ramp-up time: 1 s
Ramp-down time: 3 s
1
Activated
Not active
Not active
Not active
Not active
Not active
Ext. stop
Not active
Not active
Not active
Not active
Speed/0-10 V
Not active
Alarm
Ready
Not active
Not active
Not active
Not active
MGE OEM
100 %
Normal
67 %
Constant curve
Active
Kp: 0.5
Ti: 0.5
16-100 %
Ramp-up time: 10 s
Ramp-down time: 10 s
1
Activated
Function: Setpoint influence
Measured parameter: Other
Signal type: 0-10 V
Range: 0-100
Unit: %
Not active
Not active
Not active
Not active
Ext. stop
Not active
Reverse rotation
Not active
Not active
Speed/0-10 V
Linear
Alarm
Ready
Not active
Not active
Not active
Not active
61