A2 00
Automatic reclosing after the pause time
00
OFF (doesn't automatically relock)
01
15
NUMBER of reclosure attempts (interrupted by photocell) before finally staying open
-
99
try to close without limitation to the number of attempts
NOTE: parameter
To enable automatic reclosing you must set this parameter to a different number from
parameter the value
01
between
setting the value
would re-open but would no longer close (only performs one reclosing attempt).
NOTA: the value of the parameter
49
has a maximum value equal to that of parameter
A3 00
Reclosing after blackout
00
OFF (does not reclose when the power is restored)
01
ON (recloses when the power is restored)
NOTE: parameter
If this parameter is set to
5 s (even if not enabled on parameter
during the reclosing because it guarantees that the gate is closed when the supply voltage is restored.
After the blackout the position of the wings is unknown, and if the phase shift in closure is enabled,
reclosing takes place one wing at a time in "position recovery" mode.
A4 00
STEP-BY-STEP (PP)
00
OPENS - STOPS - CLOSES - STOPS - OPENS
01
PP CONDOMINIUM, command PP refreshes the rest time from fully opened
02
PP CONDOMINIALE, command PP closes from fully opened
03
OPENS – CLOSES – OPENS - CLOSES
04
OPENS – CLOSES – STOPS – OPENS
NOTE: parameter
Condominium means that the command PP is ignored when opening.
In installations where multiple users may arrive at the same time, and therefore trigger the radio
control while the gate is operating, is useful to ensure the completion of the opening: it is possible to
prevent two activations by different users from reversing the motion by closing the gate.
By setting the parameter to the value
command does not perform a closure but restarts the count of the rest time.
A5 00
Pre-flashing
00
OFF (the flashing light is only on when there is movement)
01
10
DURATION IN SECONDS of the early activation of the flashing
-
99
not performed when opening; 5 seconds of pre-flashing when closing
NOTE: parameter 5- in simplified mode
A6 00
Condominium function with PEDESTRIAN (PED)
00
OFF (pedestrian control performs AP-ST-CH-ST-AP- ...)
01
ON (pedestrian control operated when opening is ignored)
1-
in simple mode.
99
will it always reclose after the pause time. However, if you set a number
15
and
, is the maximum number of attempts at reclosing carried out. For example, by
01
, f a person crosses the ray of the reversal photocells when reclosing, the wings
3-
in simplified mode.
01
lthe control unit, when on, performs the reclosing after a pre-flashing lasting
6-
in simplified mode
49
is subordinate to that selected for parameter
a2
A5
). This feature is useful when there is no longer the supply voltage
01
, if the gate is open, the activation of the step-by-step
.
00
; only by
a2
; parameter
29