Restoring The Standard Factory Parameters; Change Between Standard/Extended Parameters Mode - Roger Technology AG/CTRL AGILIK Instrucciones Y Advertencias Para El Instalador

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 80
5.2.2
Restoring the standard factory
parameters
NOTE: this procedure can be performed only if a
data protection password has not been set.
Cut off the power supply of the control unit, keep
the keys UP and DOWN pressed, then restore the
PARAMETER
AND
STANDARD
VALUE
0- 02
Barrier length selection
1- 00
Automatic closure
2- 30
Break time
Automatic closure after
3- 00
restoring power supply
4- 00
Barrier light setup
5- 00
Pre-flashing
6- 00
Step-by-step input setup
7- 02
Flashing light setup
Duration of acceleration
8- 10
phase while opening
Speed during the opening
9- 04
movement
Duration of deceleration
A- 10
phase while opening
Duration of deceleration
b- 10
phase during closing
Speed during the closing
C- 04
movement
Duration of deceleration
d- 10
phase while closing
Anti-crushing function
e- 09
adjustment
f- 08
Brake adjustment
Position of the barrier body
- 01
in relation with the passage
FUNCTION
DISPLAY
power supply and hold the keys pressed: after 4
seconds, on the display appears
indicating that the values were restored.
5.2.3
The control unit allows two configuration modes:
VALUE
ON
up to 3m.
00
from 3m to 4.5.
01
from 4.5m to 6m
02
Disabled
00
01 -15 NUMBER of closing attempts (interrupted by the
photocell) before leaving it opened
always try to close
99
00 -90 Break Time
92 -99 2 minutes...9 minutes of time-out
disables the closing after restoring the power supply
00
enables the closing after restoring the power supply
01
always off
00
always on
01
on while it is closed, blinking when it is moving
02
quick flashing while it stands still, blinking when it is moving
03
disabled.
00
01 -60 pre-flashing seconds
5 seconds of pre-flashing while closing
99
open stop close stop open stop close ...
00
shared, restores the break time
01
shared, closes the barrier from completely open position
02
open close open close ...
03
open close stop open ...
04
fixed
00
slow blinking activation
01
slow blinking while opening, quick blinking while closing
02
01 -10 01 = short acceleration period ...
10 = prolonged acceleration period
01 -10 01 = minimum speed .... 10 = maximum speed
01 -10 01 = short deceleration period ...
10 = prolonged deceleration period
01 -10 01 = short acceleration period ...
10 = prolonged acceleration period
01 -10 01 = minimum speed ... 10 = maximum speed
01 -10 01 = short deceleration period ...
10 = prolonged deceleration period
01 -09 01 = fast response ... 09 = slow response
disabled.
10
01 -10 01 = sudden braking ... 10 = soft braking
placed to the left, watching the passage from the inside
00
placed to the right, watching the passage from the inside
01
Change between standard/
extended parameters mode
DESCRIPTION
rES-
blinking,
27

Publicidad

Tabla de contenido
loading

Tabla de contenido