Photocells Test Mode; Error Signals; Mechanical Unlock Enabling - Roger Technology AG/CTRL AGILIK Instrucciones Y Advertencias Para El Instalador

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 80
a series of noisy oscillations that may affect the
mechanics of the barrier.
7

PHOTOCELLS TEST mode

To enable the test mode of the photocells connect
the supply of the photocells transmitter to the
terminal SC (no. 11, figure 8) instead of terminal no.
13 and set the parameter
configuration.
For every transmitted command, the control unit
turns off and on the photocells and makes sure
that the contact status changes accordingly: if all
goes well, the command will activate the engine;
otherwise, the system remains locked as there is a
fault at the photocells level.
NOTE: in this mode, at the terminal SC is always
present a voltage of 24Vdc, therefore that output can
no longer be used for the open door light.
If the battery is installed, it is advisable to connect
the supply of all external devices to terminal 11
(SC, see figure 9) and set
both settings, the supply to terminal 11 (SC) is cut
off when the automation is still in fully opened or
fully closed mode and it is powered by battery, thus
limiting the consumption of the back-up battery. If
A8  04
using the setting
photocells input will be activated.
8

Error signals

The operating parameters are stored in a non-
volatile memory (EEPROM) using control codes
that ensure their validity; "a possible" error at the
parameters level will be indicated on the display
and at the same time the control unit will block the
command activation.
Example: if an error should appear in parameter
21, on the display will appear the error message
21  ee
.
EE
indicates the presence of the error; the control
unit will be locked until the correct value is restored;
the operator must use the keys + and - to select the
numerical value appropriate for the installation and
then save it.
NOTE: if an error should appear, on the display will
always appear the "extended mode" numbering
indicated in the table on paragraph 10, even if
activated the simplified mode.
The following errors regarding the motor control will
be displayed:
OF  St
calibration error (offset), system blocked.
Cut off the power supply and wait for 10"
then repeat the calibration.
30
A8  O2
in the extended
A8
03
A8
04
or
, the test function at the
Pr  Ot
intervention of the motor ampere level
(excessive force). In order to start the
motor press 2 times the key TEST or give 3
movement commands.
da  ta
error in the data regarding the length of the
stroke; a new setup should be performed.
The display can be unlocked to display the
parameters, by pressing the TEST key.
o  t
Motor not connected
St  oP
The mechanical release is active, or the
inspection door is open, or the STOP
button (if installed) is active for more than
3 seconds. The signal is blinking
There are also encoder-related errors:
En  E1
encoder 1 not connected; check the
connection and if the error does not
disappear, consider to replace the device
En  E2
encoder 2 not connected
En  E3
serious malfunction of encoder 1; press the
TEST key and see if it recurs or not; in this
. For
case cut off the power supply and after 5"
power up once again the control unit. If the
error persists, please replace the encoder
En  E4
serious malfunction of encoder 2. Proceed
as indicated for error
En  E5
transitory malfunction of encoder 1;
press the TEST key and see if the problem
disappears; otherwise, please replace the
encoder
En  E6
transitory malfunction of encoder 2; act as
indicated for error
En  E7
error in measuring the angle of encoder 1
En  E8
error in measuring the angle of encoder 2
In order to temporarily cancel the alarm from the
display, press the TEST key; the message will not be
displayed once the system enter in the parameters
display mode. When a command is received, if the
cause was not removed, the signal will re-appear on
the display.
9
Mechanical release enabling
When mechanically unlocking the barrier, in order
to manually move it, if the control unit is powered
up, the following functions will be performed:
• Unlocking will be signalled by blinking message
St  oP
on the display; it will disappear as soon as
the blocking situation will be restored
• The manual movement of the barrier will be
indicated by activating the flashing light and the
signalling lights on the barrier
En  E3
En  E5

Publicidad

Tabla de contenido
loading

Tabla de contenido