10.3
TEST mode
The TEST mode is used to test activation of the commands and safety devices with visual con rmation.
To activate the mode, press the TEST button with the automatic door system at rest. If the gate is moving, pressing
TEST stops the gate. Pressing the button again enables TEST mode.
If the ashing light and the gate open indicator lamp illuminate for one second each time a control is used or a
safety device is activated.
Example: STOP contact in alarm state.
No safety device in alarm state and no limit switch activated.
(Sb)
Release handle or lock open.
STOP contact (N.C.) open.
If there is no STOP switch, jumper the contact.
Sensing edge contact COS1 (N.C.) is open. Check connection.
If sensing edge is not installed, disable with
Sensing edge contact COS2 (N.C.) is open. Check connection. If sensing
edge is not installed, disable with
Photocell contact FT1 (N.C.) is open. Check connection. If photocell is
not installed, disable with
Photocell contact FT2 (N.C.) is open. Check connection. If photocell is
not installed, disable with
Both limit switches in error state.
Check connections and settings of limit switches.
If gate is open, gate open limit switch is detected.
If gate is closed, gate closed limit switch is detected.
NOTA: If one or more contacts are open, the gate will not open or close. This does not apply for the limit switch
signal state, however, which is shown on the display but does not prevent normal operation of the gate.
If more than one safety device is in alarm state, once the problem relative to the rst device is resolved, the alarm
for the next device is displayed. Any further alarm states are also displayed with the same logic.
Press the TEST button again to exit test mode.
After 10 seconds with no user input, the display returns to command and safety device state display mode.
10.4
Standby mode
POWER
The command signal status is shown on the left hand side of the
display for 5 seconds, ONLY when the respective command signal is
active (AP, CH, PP, PE, OR). For example, if the gate open command is
activated, the letters AP appear on the display.
The status of the safety devices/inputs is shown on the right hand
side of the display. The number of the terminal relative to the safety
device in alarm state ashes.
When the gate is completely open or completely closed,
shown on the display to indicate that the gate has reached the gate
open limit switch
or gate closed limit switch
.
.
.
This mode is activated after 30 minutes with no user input. The POWER
LED ashes slowly.
Press UP
, DOWN
, + , - to reactivate the control unit.
NOTE: If a safety password (only if active) is unlocked, to adjust the
parameter settings, the password is automatically reactivated in
Stand By mode.
.