Gate Open Light; Incoming Deceleration; Pedestrian Stroke Length; Pause Time For Automatic Reclosing - Roger Technology B70/1DC Instrucciones Y Advertencias Para El Instalador

Ocultar thumbs Ver también para B70/1DC:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 84
A8 00

Gate open light

00
when the gate is closed the light is off, otherwise it is on
slow flashing when opening, quick when closing, fixed from fully open, turns off twice in
01
succession every 15 seconds if the gate has stopped in the intermediate position
02
the SC output is used to supply power to the photocells and perform the test on them
The output SC in battery mode does not power the external loads when the door are fully
03
open or fully closed; in the presence of network voltage the output SC always supplies power
04
as for value 03, and in addition even the phototest function is run
11 04
Incoming deceleration motor
01
05
deceleration duration (1 = rapid deceleration ... 5 = slow deceleration)
-
01
A low value (
will start the slowdown very much in advance.
NOTE: these parameters can be changed even after you have programmed the stroke.
15 50

Pedestrian stroke length

01
99
PERCENTAGE of the total stroke
-
As a production standard it opens to half the stroke.
21 30

Pause time for automatic reclosing

00
90
SECONDS
-
92
99
from 2 to 9 MINUTES
-
NOTE: parameter
When one of the photocells is obscured the timer is reset and the count restarts upon the return of
the safety protection at pause.
27 03
Time taken to move back after the intervention of the safety edge or the anti-crushing protection
00
60
SECONDS
-
Establishes how many seconds the reversal operation on obstacle lasts; set to a value high enough
to reach the opening limit switch it also performs automatic reclosing according to parameter
30 05
Fine adjustment of the impact forces (combined with par. 31)
motor torque reduction 1 = -8%, 2 = -6%, 3 = -4%, 4 = -2%
01
09
5 = the motor torque is at the factory setting
-
motor torque increase 6 = +2%, 7 = +4%, 8 = +6%, 9 = +8%
NOTE: increasing / decreasing the parameter increases / decreases the nominal torque of the motor,
and accordingly adjusts the force of impact. During the path program the controller stores the
consumption of current of the motor, and uses this information to always give a margin more than
what is needed for the actual path. However, this margin is reduced to 0 if you set parameter
01
. The value
by environmental effects such as strong winds or particularly cold weather.
) involves quick deceleration, just before reaching the limit switch, a high value (
2-
in simplified mode.
01
is therefore to be used only for particularly light installations that are not affected
05
)
49
.
30
to
33