Tabla D.8 Calibre del cable y especificaciones de torque (clase de 600 V trifásica)
Modelo de
variador
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
5A0003
⊖, ⊕1, ⊕2
5A0004
5A0006
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
⊖, ⊕1, ⊕2
5A0009
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
⊖, ⊕1, ⊕2
5A0011
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
⊖, ⊕1, ⊕2
5A0017
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
⊖, ⊕1, ⊕2
5A0022
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
5A0027
⊖, ⊕1, ⊕2
5A0032
B1, B2
YASKAWA ELECTRIC SISP C710616 41E Variador de CA YASKAWA A1000 Manual Técnico
Calibre recomendado
Terminal
2
mm
(AWG, kcmil)
Rango de cables
2
mm
(AWG, kcmil)
2.5
2.5 a 6.0
(14)
(14 a 10)
2.5
2.5 a 6.0
(14)
(14 a 10)
2.5 a 6.0
–
(14 a 10)
2.5 a 6.0
–
(14 a 10)
6.0
2.5 a 6.0
(10)
(14 a 10)
2.5
2.5 a 6.0
(14)
(14 a 10)
2.5
2.5 a 6.0
(14)
(14 a 10)
2.5 a 6.0
–
(14 a 10)
2.5 a 6.0
–
(14 a 10)
6.0
4.0 a 6.0
(10)
(12 a 10)
6.0
2.5 a 16
(10)
(14 a 6)
2.5
2.5 a 16
(14)
(14 a 6)
2.5 a 16
–
(14 a 6)
2.5 a 6.0
–
(14 a 10)
10
4.0 a 6.0
(8)
(12 a 8)
6.0
6.0 a 16
(10)
(10 a 6)
6.0
6.0 a 16
(10)
(10 a 6)
6.0 a 16
–
(10 a 6)
6.0 a 10
–
(10 a 8)
10
6.0 a 10
(8)
(12 a 8)
10
6.0 a 16
(8)
(10 a 6)
6.0
6.0 a 16
(10)
(10 a 6)
6.0 a 16
–
(10 a 6)
6.0 a 10
–
(10 a 8)
10
6.0 a 10
(8)
(10 a 6)
16
16 a 25
(6)
(6 a 4)
16
16 a 25
(6)
(6 a 4)
16 a 25
–
(6 a 4)
6.0 a 10
–
(10 a 8)
16
10 a 16
(6)
(10 a 6)
D.3 Estándares UL y CSA
Tamaño de
Torque de ajuste
los tornillos
N·m (lb.in.)
1.2 a 1.5
M4
(10.6 a 13.3)
1.2 a 1.5
M4
(10.6 a 13.3)
2.1 a 2.3
M4
(18.6 a 20.4)
2.0 a 2.5
M5
(17.7 a 22.1)
3.6 a 4.0
(31.8 a 35.4)
M5
2.7 a 3.0
(23.9 a 26.6)
5.4 a 6.0
M6
(47.8 a 53.1)
3.6 a 4.0
(31.8 a 35.4)
M5
2.7 a 3.0
(23.9 a 26.6)
5.4 a 6.0
M6
(47.8 a 53.1)
5.4 a 6.0
M6
(47.8 a 53.1)
2.7 a 3.0
M5
(23.9 a 26.6)
5.4 a 6.0
M6
(47.8 a 53.1)
D
789