Fig. 40:
Filter unit connection/main supply
Robert Bosch GmbH
Commissioning | TCE 4460 | 53
4.4

Electrical connection

DANGER – Risk of electric shock if connec-
tions are not or not correctly grounded or
from incorrect mains voltage.
Incorrect phase, neutral and ground con-
nections can cause electric shocks, heart
failure and fatalities!
Work on electrical installations or equip-
ment is only to be performed by qualified
electricians or trained personnel under
the guidance and supervision of an elec-
trician.
Even minor work on the electrical system
is only to be performed by appropriately
trained and qualified personnel.
The TCE 4460 is only to be connected
to the power supply if the mains voltage
available corresponds to the rated voltage
given on the rating plate.
Check the grounding before connecting
the TCE 4460.
Use the type of power cord specified for
the country concerned.
i
The TCE 4460 must be connected to a standard
electrical system provided with a residual-current-
operated circuit breaker with a connection cross-
section of at least 3 mm conforming to European
standards. The customer is responsible for providing
fuse protection for the mains connection.
i
A two-pole residual-current-operated circuit breaker
of type „C" must always be used to provide fuse pro-
tection for the mains connection. Single-pole circuit
breakers are not permissible.
i
The temperature and ambient conditions specified in
the Technical Data must be observed for operation.
1. Depending on the mains voltage, have a qualified
electrician fit a country-specific single-phase or
three-phase connector (see Tab. 3-4).
en
|
1 695 105 428
2013-11-04