Setting reverse time after activation of sensing edge or obstacle detection
(crush prevention)
This sets the reverse manoeuvre time after activation of the sensing edge or the obstacle detection
system.
From 0 to 60 s.
Set electric lock activation lead time
Sets the electric lock activation time before any manoeuvre.
N.B.: parameter visible only if electric lock is enabled
From 0 to 2 s.
Enable electric lock
Sets duration of electric lock activation time.
N.B.: parameter visible only if electric lock is enabled
Disabled.
This parameter must be set to a value higher than parameter
Disabled.
Enabled.
of power supply disturbance and optimise motor control.
Set motor torque during open/close manoeuvre
This parameter must always be equal to or less than the value set for parameter
1 = minimum motor torque ... 8 = maximum motor torque.
Set motor torque during deceleration
1 = minimum motor torque ... 8 = maximum motor torque.
Set motor torque boost at start of manoeuvre
1 = minimum motor torque ... 8 = maximum motor torque.
Set initial acceleration when opening/closing (soft-start)
Disabled.
Enabled. The gate accelerates slowly and progressively at the start of the manoeuvre.
Enabled. The gate accelerates even more slowly and progressively at the start of the manoeuvre.
ded for heavy gates.
Set motor torque after activation of sensing edge or encoder
Disabled. Torque applied is the value set for parameter
1 = minimum motor torque ... 8 = maximum motor torque.
Enable maximum torque boost at start of manoeuvre
ble period of time to allow the gate to start moving.
From 0 to 20 s.
Set open/closed stop approach distance
Disabled.
.
.
(if enabled).
/
). Setting a value of
.
.
is not recommen-
-
63