Setting motor torque

Use values below
SOLO ONLY for particularly lightweight installations not exposed to severe
weather conditions (strong winds or very cold temperatures).
05= 0%
06= +8%; 07= +16%; 08= +25%; 09= +35% (increased motor torque = reduced sensitivity).

Setting obstacle impact force sensitivity

01 = minimum obstacle impact force ... 10 = maximum obstacle impact force
N.B.
Medium motor torque. Recommended setting for adjusting force settings correctly.
11 = minimum obstacle impact force ... 18 = maximum obstacle impact force.
Maximum motor torque. May only be used if the door is equipped with a sensing edge.
Setting opening start acceleration
Setting closure start acceleration
01= the door accelerates rapidly at start of manoeuvre ... 10= the door accelerates slowly and progres
sively at start of manoeuvre.

Enabling maximum torque boost at start of manoeuvre

Disabled.
Always enabled at start of opening manoeuvre (including position recovery). The motor boost function
is ONLY enabled for closing manoeuvres if the door position is known and the door is at least 0.5 me
tres from the completely closed position.
Enabled for all starts (including position recovery).
Enable motor torque during position recovery
Adjust motor torque with parameter
and
The response of the obstacle detection system depends solely on the values set for parameters
and
.
The response of the obstacle detection system depends on the values set for parameters
and
and on the maximum current value stored during travel acquisition.
The response of the obstacle detection system is a 70% reduction in maximum torque for a period of 1 s.
The response of the obstacle detection system is a 100% reduction in maximum torque for a period of 3 s.
Setting opening speed (%)
Setting closure speed (%)
Setting number of automatic closure attempts after activation of sensing edge
or obstacle detection (crush protection)
No automatic closure attempts.
From 1 to 3 automatic closure attempts.
We recommend setting a value equal to or lower than the value set for parameter
.
Automatic closure is only performed if the door is completely open.
58