Cable Routing; Cable Bending Radius; Electrical Installation; General Information For The Connection - Kübler Sendix 5814FS2 Manual De Instrucciones

Ocultar thumbs Ver también para Sendix 5814FS2:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

4.1.8 Cable Routing

Route the measuring system cable free of any tension, so
that no additional force is applied on the measuring system.
Consider the minimum bending radii of the connection cable.
Consider the information for EMC-compliant installation in
chapter Electrical Installation [} 52].

4.1.8.1 Cable Bending Radius

R
min
ø d
The following minimum values apply for encoders with cable
outlet (R
):
min
R
min
Fixed installation
75 [2.95]
Flexible use
110 [4.33]
BA Sendix® 58xxFS2 / 58xxFS3 - R60049.0009 - 03

4.2 Electrical Installation

4.2.1 General Information for the Connection

ATTENTION
Destruction of the device
Before connecting or disconnecting the signal cable, always
disconnect the power supply and secure it against switching
on again.
General safety instructions
Make sure that the whole plant remains switched off during
the electrical installation.
• Make sure that the operating voltage is switched on or off
simultaneously for the device and the downstream device.
• Use a PELV supply voltage source according to
EN 60204-1 with the proper operating voltage and the max-
imum permissible output current.
NOTICE
EN - 51

Publicidad

Tabla de contenido
loading

Tabla de contenido