Descargar Imprimir esta página

emmeti MIRAI - SMI 4.0 Manual De Instrucciones página 100

Publicidad

Idiomas disponibles

Idiomas disponibles

5. INSTALLATION
Default
Parameter
Description
value
Operational status in Off condition:
C402
1
0= All functions/outputs are Off except frost protection
1= Only DHW production and frost protection remains active
C403
0
Not Used
Pump2relaunch circulator activation:
0= Radiant system only
C404
0
1= For both the radiant system and SetPoint 2
2= SetPoint 2 only
Set Point 2 climate curve activation:
C405
O (Off)
0 (Off)= Disable
1 (On)= Activate
C406
1
Not Used
C407
1
Do not edit
Operation of the internal pump Pump1 with compressor off for temp. of Target satisfied:
0 = Always active
C408
0
1 = Assays at regular intervals of 15 min
2 = Assays at automatically calculated intervals
C409
1
Not Used
Water flow meter configuration
0 = No meter (shows alarm AL09 but the HP works regularly)
C410
10
10 = Liter counter (10 imp/l)
37 = Water flow meter VORTEX (37 imp/l)
Default
Parameter
Description
value
External temperature probe
-
-
alternative to that on the machine
C420
0
Not Used
Domestic hot water temperature probe
C421
0
(connect to Eco Hydro Kit)
C422
0
Ambient thermostat
Pulsed outlet water flow counter
C423
2
(connect to Eco Hydro Kit)
C424
0
Compressor frequency limitation
Remote Summer/Winter
C425
0
Closed contact = Winter
C426
0
Set point 2
DHW Integration electrical reset consent
(connect to Eco Hydro Kit)
C427
1
L phase in call
Install a support relay between the contact on the board and
the external load.
Additional heater consent
(connect to Eco Hydro Kit)
C428
1
L phase in call
Install a support relay between the contact on the board and
the external load.
PdC signal in alarm
C429
1
Contact closed in alarm
Relaunch pump (connect to Eco Hydro Kit)
C430
1
L phase in call
Consent to 3-way DHW valve
C431
0
(connect to Eco Hydro Kit)
L phase in call
C432
0
Not Used
C433
0
Not Used
Connection of the RS-485 serial interface
Modbus connection protocol (RTU):
- Baudrate: 9600
-
-
- Frame Settings: E 8.1
- Address: 1
- Timeout: 1000
(*) Closing current, ground 0.5 mA (SELV: ultra low safety voltage)
SIGNAL CABLE (<24V): BUS-SCS cable consisting of 2 flexible conductors, with a cross-section of 0.50 mm
DATA TRANSMISSION CABLE (RS-485): 1 X 2 X AWG 24 FLEX S(FTP) LSZH RS485 MODBUS serial bus cables for Canbus and Modbus applications. Belden type 14S7KVZ or equivalent.
The shield must be grounded at one end of the cable only.
CONTROL CABLE (230 V):
Electric cable with section 1.5 mm
ATTENTION:
The system must be built in compliance with the relative project and in compliance with the regulations in force in the place of installation.
It is absolutely forbidden to pass signal and data transmission cables together with power cables with voltages> 50 V.
100
RECIPE 2 (C400=2)
CONFIGURABLE PARAMETERS
TERMINAL BLOCK PCB CONNECTION SPECIFICATIONS
2
.
Rif I/O
Electrical characteristics Cable type
Outdoor
A+ / A-
NTC 10k at 25°C
temp.
-
B+ / B-
-
100
C+ / C-
NTC 10k at 25°C
Digital Input
101
D+ / D-
(dry contact) *
Digital Input
102
E+ / E-
(dry contact) *
Digital Input
103
F+ / F-
(dry contact) *
Digital Input
104
G+ / G-
(dry contact) *
Digital Input
105
H+ / H-
(dry contact) *
Live output
200
R1
230V~ max 8A
201
T1
-
Output not live (dry
202
M1 / M2
contact)
Live output
203
P2
230V~ max 2A
Voltage output 230V~
204
W1
max 2A
Voltage output 230V~
205
U1
max 2A
206
X+ / X-
-
Serial port
RS-485
- + G
RS-485
2
, twisted with sheath and unshielded.
EN
EN
SIGNAL
-
SIGNAL
SIGNAL
SIGNAL
SIGNAL
SIGNAL
SIGNAL
COMAND
-
SIGNAL
COMAND
COMAND
COMAND
-
DATA
TRANSMISSION

Publicidad

loading

Este manual también es adecuado para:

Eh0618dcEh1018dcEh1218dcEh1618dcEh1718d3