8. USER SECTION: OPERATION

8.17 Active alarms

In the event of an alarm, the icon
Access the AL menu to view the active alarms
Recipes 1 and 3
The voltage output 203 (P2) of the TERMINAL BLOCK PCB is set up to
supply (phase L) an external "Heat pump in alarm" signal.
PdC in allarme
P2 out
Recipes 2 and 4
The output 202 (M1 / M2) of the TERMINAL BLOCK PCB is set to give
consent to an external "Heat pump in alarm" signal.
M1 out
M2 out

8.18 Alarm history

All recipes
On the SMART-MT, in addition to displaying the active alarms (AL menu),
you can view the history of the last 10 alarms (000 menu).
The instant an alarm appears, the following is saved:
- the alarm code (Par LAL0),
- the date (Par LAL1),
- the hour (LAL2 pair)
- external air temperature (LAL3)
- the temperature of the water entering the PdC (LAL4)
- the temperature of the water leaving the PdC (LAL5)
- the electrical power absorbed by the PdC, if available, otherwise Com-
pressor operation step (LAL6).
On the CAL0 Parameter, select the chronological position (from 0 to 9)
that you want to consult, then view the saved data (LAL0 ÷ LAL6).
on the SMART-MT appears.
L N
POWER
L N
PdC in allarme
8.19 High temperature radiant system
alarm input
Recipe 13
Input 103 (F + / F-) of the TERMINAL BLOCK PCB is configured as a radiant
system high temperature alarm input, therefore:
Closed contact
High temperature
alarm input Radiant
system
Alarm AL08 is activated and the compressor stops.
The circulator, on the other hand, activates for 5 min every 30 min in an
attempt to reset the alarm.

8.20 Low pressure systrem alarm input

Recipe 13
Input 104 (G + / G-) of the TERMINAL BLOCK PCB is configured as system
low pressure alarm input, therefore:
Closed contact
System low pressure
alarm input
Alarm AL10 is activated and both the compressor and the circulator stop.
EN
EN
135