10. CODES AND ALARMS ON PCB DISPLAY
1. DESCRIZIONE DEI COMPONENTI
10.1 Alarm codes on PCB Display
Error Code
Description
--
A0
DC Voltage Error
138
Unit
Electrical supply
Fuse CF1
EH0618DC
EH0618DC :250V 15A
EH1018DC
EH1018DC : 250V 25A
EH1218DC
EH1218DC: 250V T30A
EH1618DC
EH1618DC: 250V T30A
EH0618DC
Fuse CF3
EH1018DC
EH1218DC
250V 3A
EH1618DC
--
Fuse CF4
EH0618DC
EH0618DC :250V 3A
EH1018DC
EH1018DC : 250V 3A
MAIN PCB
Fuse CF1,2,3
EH1718D3
500V 20A
Fuse CF4
EH1718D3
250V T5A
Electrical supply
EH0618DC
EH1018DC
FAN MOTOR
EH1218DC
EH1618DC
Fuse CF6
EH1218DC: 250V
EH1218DC
EH1618DC
T3.15A
EH1618DC: 250V
T3.15A
Fuse CF7
EH1018DC
EH1018DC: 250V T3.15A
EH1218DC
EH1218DC: 250V T3.15A
EH1618DC
EH1618DC: 250V T3.15A
EH0618DC
EH1018DC
PUMP
EH1218DC
EH1618DC
REACTOR
EH0618DC
EH1018DC
MAIN PCB
EH1218DC
EH1618DC
EH1718D3
MAIN PCB
EH1718D3
INVERTER PCB
PCB DISPLAY
Interested party
Verification method
Check the power supply.
Check the electrical
continuity with a tester
[fig. 1]
Check the electrical
continuity with a tester
[fig. 1]
Check the electrical
continuity with a tester
[fig. 1].
Anomaly differs from the
cases described above.
Check the electrical
continuity with a tester
[fig. 1]
Check the electrical
continuity with a tester
[fig. 1]
Check the power
supply.
Run with the FAN MO-
TOR disconnected.
Check the electrical
continuity with a tester.
Run with the FAN MO-
TOR disconnected.
Check the electrical
continuity with a tester.
Run with the FAN MOTOR
disconnected.
Check the electrical conti-
nuity with a tester.
Run with the PUMP
disconnected.
Check the electrical
continuity between the
REACTOR terminals
with a tester and the
resistance value (0.1
A 20°C).
Check the FAN MOTOR
voltage with a tester.
Check the PUMP volt-
age with a tester.
-------
-------
EN
EN
Troubleshooting
Make sure the power supply is
correct.
If the fuse CF1 has blown, replace
the MAIN PCB.
If the CF3 fuse has blown, replace
the MAIN PCB.
If the CF4 fuse has blown, replace
the MAIN PCB.
Replace the MAIN PCB.
If the fuse CF1 or 2 or 3 has blown,
replace the MAIN PCB.
If the CF4 fuse has blown, replace
the MAIN PCB.
Make sure the power supply
is correct.
If the same error code appears,
the MAIN PCB or the PUMP
must be replaced. If a different
error code appears, replace the
FAN MOTOR.
If the fuse CF6 has blown,
replace the fuse.
If the CF7 fuse has blown,
replace the fuse.
If the same error code appears,
the MAIN PCB or FAN MOTOR
must be replaced. If a different
error code appears, replace the
PUMP.
If there is no electrical continu-
ity on the REACTOR, replace it.
If the voltage is abnormal,
replace the MAIN PCB.
Replace the MAIN PCB.
Replace the INVERTER PCB.