5. INSTALLATION
Default
Parameter
value
C402
1
C403
0
C404
0
C405
O (Off)
C406
1
C407
0
C408
0
C409
1
C410
10
Default
Parameter
value
-
-
C420
0
C421
0
C422
0
C423
0
C424
0
C425
0
C426
0
C427
0
C428
0
C429
0
C430
0
C431
0
C432
0
C433
0
-
-
-
-
(*) Closing current, ground 0.5 mA (SELV: ultra low safety voltage)
SIGNAL CABLE (<24V): BUS-SCS cable consisting of 2 flexible conductors, with a cross-section of 0.50 mm
DATA TRANSMISSION CABLE (RS-485): 1 X 2 X AWG 24 FLEX S(FTP) LSZH RS485 MODBUS serial bus cables for Canbus and Modbus applications. Belden type 14S7KVZ or equivalent.
The shield must be grounded at one end of the cable only.
CONTROL CABLE (230 V):
Electric cable with section 1.5 mm
ATTENTION:
The system must be built in compliance with the relative project and in compliance with the regulations in force in the place of installation.
It is absolutely forbidden to pass signal and data transmission cables together with power cables with voltages> 50 V.
98
RECIPE 1 (C400=1) - Factory configuration
CONFIGURABLE PARAMETERS
Description
Operational status in Off condition:
0= All functions/outputs are Off except frost protection
1= Only DHW production and frost protection remains active
Not Used
Pump2relaunch circulator activation:
0= Radiant system only
1= For both the radiant system and SetPoint 2
2= SetPoint 2 only
Set Point 2 climate curve activation:
0 (Off)= Disable
1 (On)= Activate
Not Used
Domestic Hot Water:
0= Produced by Eco Hot Water
1= Produced by the PdC connected to the heat exchanger of an accumulation
2= Not usable
Operation of the internal pump Pump1 with compressor off for temp. of Target satisfied:
0 = Always active
1 = Assays at regular intervals of 15 min
2 = Assays at automatically calculated intervals
Not Used
Not Used
TERMINAL BLOCK PCB CONNECTION SPECIFICATIONS
Description
External temperature probe
alternative to that on board the machine
Not Used
Domestic hot water temperature probe
Ambient thermostat
Remote On/Off
Contact Closed = On
Compressor frequency limitation
Remote Summer/Winter
Closed contact = Winter
Set point 2
Additional heater consent
L phase in call
Install a support relay between the contact on
the board and the external load.
Not Used
Consent to Eco Hot Water
Contact closed on call
PdC signal in alarm
Phase L in presence of alarms
Consent to 3-way DHW valve
L phase in call
Not Used
Not Used
Relaunch pump
Phase L when the PdC circulator is active
Connection of the RS-485 serial interface
Modbus connection protocol (RTU):
- Baudrate: 9600
- Frame Settings: E 8.1
- Address: 1
- Timeout: 1000
2
.
Rif I/O
Electrical characteristics
Outdoor
A+ / A-
NTC 10k at 25 °C
temp.
-
B+ / B-
100
C+ / C-
NTC 10k at 25 °C
Digital input (dry
101
D+ / D-
contact) *
Digital input (dry
102
E+ / E-
contact) *
Digital input (dry
103
F+ / F-
contact) *
Digital input (dry
104
G+ / G-
contact) *
Digital input (dry
105
H+ / H-
contact) *
Voltage output 230V~
200
R1
max 8A
201
T1
Output not live (dry
202
M1 / M2
contact)
Voltage output 230V~
203
P2
max 2A
Voltage output 230V~
204
W1
max 2A
205
U1
206
X+ / X-
Voltage output 230V~
-
P1
max 2A
Serial port
RS-485
- + G
RS-485
2
, twisted with sheath and unshielded.
EN
EN
EN
EN
Cable type
SIGNAL
-
-
SIGNAL
SIGNAL
SIGNAL
SIGNAL
COMAND
-
-
SIGNAL
COMAND
COMAND
-
-
-
-
COMAND
DATA
TRANSMISSION