6. TYPE OF INSTALLATION
1. DESCRIZIONE DEI COMPONENTI
6.3 DIAGRAM 3
HYDRAULIC CONNECTION
MIRAI-SMI with Eco Hydro Kit: Floor Heating, Fan Coil Cooling,
DHW Production with MIRAI-SMI and Eco Hydro Kit.
INTEGRATION boiler.
Recipe 2: C400 = 2
C410=37
C903=-20.0 (default, do not modify)
C906=1.00 (default, do not modify)
Legend
1 MIRAI-SMI
2 ECO HYDRO KIT
3 Room thermostat consent
4 Frequency Limitation Switch
5 Summer / Winter switch
6 3-way Radiant / Fan Coil valve
7 Support relay
8 Fancoil
9 Heat pump failure warning light
10 etiKa Evo boiler
11 Support relay
4 5
ATTENTION:
The system must be built in
compliance with the relative
project and in compliance with
the regulations in force in the
place of installation.
It is absolutely forbidden to pass
9
signal and data transmission
cables together with power
cables with voltages> 50 V.
1
1
SIGNAL CABLE (<24V): BUS-SCS cable consisting of 2 flexible conductors, with a cross-section of 0.50 mm
DATA TRANSMISSION CABLE (RS-485): 1 X 2 X AWG 24 FLEX S(FTP) LSZH RS485 MODBUS serial bus cables for Canbus and Modbus applications.
Belden type 14S7KVZ or equivalent. The shield must be grounded at one end of the cable only.
CONTROL CABLE (230 V):
11
8
10
Electric cable with section 1.5 mm
7
6
2
2
, twisted with sheath and unshielded.
2
.
EN
EN
3
111