Descargar Imprimir esta página

emmeti MIRAI - SMI 4.0 Manual De Instrucciones página 131

Publicidad

Idiomas disponibles

Idiomas disponibles

8. USER SECTION: OPERATION
8.10 Relaunch circulator
Recipe 1
The voltage output P1 of the TERMINAL BLOCK PCB is arranged to supply
(phase L) one relaunch pump.
Booster pump
Pompa di rilancio
P1
in
The relaunch pump is powered whenever the circulator inside the PdC is
active.
Recipes 2, 10 and 13
The voltage output 203 (P2) of the TERMINAL BLOCK PCB is configured to
supply (phase L) one relaunch pump.
Booster pump
Pompa di rilancio
203
P2
out
The relaunch pump is powered when the circulator inside the PdC is
active, except if it is heating the DHW.
In addition, by configuring the C404 Parameter, you can distinguish the
following cases:
- C404=0 (factory), relaunch pump active only for the radiant system;
- C404=1,relaunch pump active for both the radiant system and the fancoils
(Set Point 2 consent);
- C404=2,relaunch pump active only for fancoils (Set Point 2 consent);
The status of the relaunch pump is visible on Parameter L244. In addition,
on the SMART-MT, icon # 1 becomes intermittent.
L N
POWER
L N
POWER
8.11 Additional heater
The PdC is able to manage the consent to an additional heater that can
intervene to support it.
The status of the additional heater consent is visible on Parameter L245.
In addition, icon no. 5 lights up on the SMART-MT.
Recipe 1 and 10
The voltage output 200 (R1) of the TERMINAL BLOCK PCB is arranged
to supply (phase L) one electrical heater integrating the PdC, or
alternatively consent to a boiler.
WARNING:
If an electric heater is used, inlet P0 must also be supplied via
outlet 200 (R1). This is to ensure the activation of the PdC internal
circulator when the heater is powered.
L N
POWER
NOTE:
If using a boiler where dry contact is required, use a back-up relay.
Boiler etiKa Evo
200
R1 out
Recipe 2 and 13
Apply what indicated in the previous point to the voltage output 201 (T1)
of the PCB TERMINAL BLOCK
EN
EN
Electric heater
L N
etiKa Evo
POWER
131