Setting Analog Inputs - SMA FUEL SAVE CONTROLLER 2.0 Instrucciones De Uso

Ocultar thumbs Ver también para FUEL SAVE CONTROLLER 2.0:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

SMA Solar Technology AG
Destruction of gensets due to insufficient reserve power
Once the SMA Fuel Save Controller and PV power plant have stopped, the PV power plant is no longer available as
energy supplier. Now only the gensets supply the loads. If the current reserve power of the gensets is insufficient for
supplying the power required by the loads, the gensets become overloaded Sustained overload of the gensets can
result in failure of the power supply and destruction of the gensets.
• Check whether the current reserve power of the gensets is sufficient for supplying the power required by the
loads.
• If the current reserve power of the gensets is insufficient, switch off the loads or connect additional gensets. This
increases the reserve power of the gensets.
• If sufficient reserve power of the gensets cannot be ensured in operation, do not use the switch input DI 7 of the
Fuel Save Controller (Fast Stop contact of the PV power plant).
Requirement:
☐ You must be logged in as Installer.
Procedure:
1. Choose the menu Configuration Wizard via the page and menu selection.
2. In the Digital Input/Output bar, select the [Adjust] button.
3. To enable the stop of the Fuel Save Controller via switch input DI 7, activate checkbox Use digital input 7 to
stop the FSC system.
4. To disable the stop of the Fuel Save Controller via switch input DI 7, deactivate checkbox Use digital input 7 to
stop the FSC system.
5. If the checkbox Use digital input 7 to stop the FSC system is activated, configure the desired values for
stopping the Fuel Save Controller via switch input DI 7 in the dropdown lists Signal mode and Stop mode.
6. Select the [Apply] button.
7. Select the [Done] button.
8. End the system settings (see Section 7.9.1, page 67).
7.8

Setting Analog Inputs

The system settings of the Fuel Save Controller can only be adjusted when the Fuel Save Controller is in STANDBY or
ERROR mode. The operating state STANDBY can be reached by stopping the SMA Fuel Save Controller.
The system settings in the Analogue Input Configuration menu can be set for both analog inputs of the Fuel Save
Controller:
• Channel A: Voltage or current input 1 (terminals X701:1 to X701:3)
• Channel B: Voltage or current input 2 (terminals X701:4 to X701:6)
User Manual
7 System Settings
FSC20-BA-xx-20
65

Publicidad

Capítulos

Tabla de contenido
loading

Tabla de contenido