SMA Solar Technology AG
Parameter
Description
RampTmGenPwrAt-
Ramp time of the change in the
Nom
nominal genset active power in
seconds
SpntOfsPc
Setpoint offset related to the mini-
mum genset loading threshold in
%
Requirement:
☐ You must be logged in as Installer.
Procedure:
1. Go to Control Functions > Genset control functions > Minimum genset load via the page and menu
selection.
2. Set the desired parameters (see Section 4.8.3, page 20).
8.1.2
Configuring Reverse Power Protection of the Gensets
Parameter overview
Figure 31: Reverse Power Protection: Settings for reverse power protection of the gensets
User Manual
Value
Explanation
1 s to 60 s
–
-100% to 100%
–
8 System Control
Default
value
10 s
0 %
FSC20-BA-xx-20